6
RT-SVX33E-EN
Model Number Description
H
=
Clogged Filter Switch, Fan Failure
Switch, Discharge Air Sensing
and Condensate Drain Pan
Overflow Switch
Digit 26 - System Monitoring
Controls
0
=
No Monitoring Controls
A
=
Demand Control Ventilation
(CO
2
)
10
B
=
FDD (Fault Detection and
Diagnostics)
C
=
FDD (Fault Detection Diagnostics)
& Demand Control Ventilation
(CO
2
)
10
Digit 27 - Unit Hardware
Enhancements
0
=
No Enhancements
1
=
Stainless Steel Drain Pan
Digit 28 - Short Circuit Current
Rating
0
=
Standard SCCR
A
=
65kA SCCR Option
11
,
12
Digit 31 - Advanced Unit
Controls
0
=
Standard Unit Controls
1
=
Human Interface
14
Note:
Most Factory Installed Options
available for Downflow Air
Discharge units only. Please verify
with ordering system for
availability.
Model Number Notes
1.
Some field set up required.
2. Available factory installed on
downflow AND horizontal units.
Verify with ordering system.
3. Through-the-base electrical
option or Horizontal-Side Access
must be ordered with either unit
mounted disconnect or circuit
breaker.
4. Unit mounted disconnect and
circuit breakers are mutually
exclusive of each other.
5. Must be ordered with Through-
the-Base Electrical option or
Horizontal-Side Access and either
Unit Mounted Disconnect or
Circuit Breaker.
6. ReliaTel Options Module is
required when ordering the
following accessories: Clogged
Filter Switch, Fan Fail Switch,
Condensate Overflow Switch,
Discharge Air Sensing Kit, Frostat,
Ventilation Override, Smoke
Detector, Dehumidification and
Modulating Gas Heat Furnace.
7.
Requires ReliaTel Options Module.
8. Option cannot be ordered in
conjunction with field installed
economizer on downflow units.
Must be factory installed. The
return air smoke detector may not
fit up or work properly on the
Voyager units when used in
conjunction with 3
rd
party
accessories (such as bolt on heat
wheels, economizers, and power
exhaust). Do not order the return
air smoke detectors when using
this type of accessory.
9. Supply and/or return smoke
detector may not be used with the
plenum smoke detector.
10. Demand Control Ventilation
Option includes wiring only. The
C0
2
sensor is a field-installed only
option.
11. Only available where MOP is
above 60A.
12. 575 VAC option is 25kA.
13. Standard filters are not available
with Low Leak Economizers.
14. Human Interface is standard with
FDD (Fault Detection Diagnostics).