54
RT-SVX25C-EN
Troubleshooting
4. Locate the RTRM (J6). Connect two (2) wires to terminals J6-1 and 2.
5. Connect the sensor (OAS) using two wire nuts to the two (2) field supplied wires that were
connected to terminals 1 and 2 on J6.
Unit Economizer Control (ECA) Troubleshooting ReliaTel Control
Verify Economizer Status by Economizer Actuator (ECA) LED indicator:
•
OFF: No Power or Failure
•
ON: Normal, OK to Economize
•
Slow Flash: Normal, Not OK to Economize
•
Fast Flash - 1/4 Second On / 2 Seconds Off:
–
Error Code: Communications Failure
•
Pulse Flash: 1/30 Second On / 1/4 Second Off: (2 Seconds between pulse sequences)
Error Code:
•
1 Flash: Actuator Fault
•
2 Flashes: CO2 Sensor
•
3 Flashes: RA Humidity Sensor
•
4 Flashes: RA Temp Sensor
•
5 Flashes: OA Quality Sensor
•
6 Flashes: OA Humidity Sensor
•
7 Flashes: OA Temp Sensor
•
8 Flashes: MA Temp Sensor
•
9 Flashes: RAM Fault
•
10 Flashes: ROM Fault
•
11 Flashes: EEPROM Fault