Installation
Filter Installation
Each unit ships with 2 inch filters installed. The quantity of filters is determined by unit size. Access
to the filters is obtained by removing the indoor fan access panel.
Refer to the unit Service Facts (shipped with each unit) for filter requirements.
Note:
Do not operate the unit without filters.
Field Installed Power Wiring
An overall dimensional layout for the standard field installed wiring entrance into the unit is
illustrated in
Figure 2, p. 14
and
Figure 4, p. 15
. To insure that the unit’s supply power wiring is
properly sized and installed, follow the guidelines outlined below.
Note:
All field installed wiring mustconform to NEC guidelines as well as state and Local codes.
Verify that the power supply available is compatible with the unit’s nameplate ratings. The available
supply power must be within 10% of the rated voltage stamped on the nameplate. Use only copper
conductors to connect the power supply to the unit.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper
conductors may result in equipment damage. Failure to do so may cause damage to the
equipment.
Note:
If the unit is not equipped with an optional factory installed nonfused disconnect switch or
circuit breaker, a field supplied disconnect switch must be installed at or near the unit in
accordance with the National Electrical Code (NEC latest edition).
Main Unit Power
Standard Wiring
The electrical service must be protected from over current and short circuit conditions in
accordance with NEC requirements.
Figure 11. Condensate trap installation