38
PKGP-PRC003-EN
Electrical
Data
Table ED-1 — Unit Wiring
Standard Indoor Fan Motor
Oversize Indoor Fan Motor
Optional Belt Drive Indoor Fan Motor
3
Unit
Minimum
Maximum Fuse
Minimum
Maximum Fuse
Minimum
Maximum Fuse
Unit
Operating
Circuit
Size or Maximum
Circuit
Size or Maximum
Circuit
Size or Maximum
Tons
Model No.
Voltage Range
2
Ampacity
Circuit Breaker
1
Ampacity
Circuit Breaker
1
Ampacity
Circuit Breaker
1
WSC036A1
187-253
26.2
40
28.6
45
N/A
N/A
3
WSC036A3
187-253
19.1
30
21.5
30
21.8
30
WSC036A4
414-506
9.9
15
11.1
15
11.3
15
WSC036AW
517-633
8.3
15
8.9
15
8.9
15
WSC048A1
187-253
39.7
60
41.8
60
N/A
N/A
WSC048A3
187-253
24.4
35
26.5
40
25.8
40
4
WSC048A4
414-506
12.1
15
13.7
20
12.9
20
WSC048AW
517-633
10.1
15
10.9
15
10.3
15
WSC060A1
187-253
48.7
60
50.4
60
N/A
N/A
WSC060A3
187-253
32.6
50
34.3
50
31.4
50
5
WSC060A4
414-506
16.6
25
16.9
25
16.2
25
WSC060AW
517-633
13.1
20
13.7
20
12.7
20
WSC072A3
187-253
32.2
50
33.5
50
—
—
6
WSC072A4
414-506
16.6
25
17.2
25
—
—
WSC072AW
517-633
12.5
15
13.5
20
—
—
WSC090A3
187-253
41.4
60
45.8
60
—
—
7½
WSC090A4
414-506
21.9
35
24.0
35
—
—
WSC090AW
517-633
16.8
25
18.8
25
—
—
WSC120A3
187-253
50.4
60
57.5
70
—
—
10
WSC120A4
414-506
26.4
35
29.9
35
—
—
WSC120AW
517-633
21.0
25
23.9
30
—
—
Notes:
1. HACR breaker per NEC.
2. Heater KW ratings are at 208-240volt for 208-230 volt units.
3. Optional Belt Drive motor applies to 3-5 ton models only.
The standard motor for 6-10 ton models is belt drive.