PKGP-PRC003-EN
23
Performance
Data
(5 Ton)
Table PD-12 — Belt Drive Evaporator Fan Performance — 5 Ton — WSC060A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied Low Static Drive (1
)
1-HP Standard Motor & Drive
1600
—
—
703
0.36
757
0.41
806
0.47
854
0.52
899
0.58
944
0.65
985
0.73
1023
0.79
1060
0.86
1800
706
0.42
760
0.47
815
0.54
861
0.60
904
0.66
947
0.72
988
0.78
1028
0.86
1067
0.94
1104
1.02
2000
773
0.57
821
0.62
873
0.69
918
0.76
958
0.83
998
0.90
1036
0.96
1073
1.02
1111
1.10
1147
1.19
2200
840
0.75
885
0.80
930
0.87
977
0.95
1016
1.03
1053
1.10
1089
1.17
1124
1.24
1158
1.31
1191
1.39
2400
909
0.96
950
1.02
990
1.08
1034
1.16
1074
1.25
1110
1.00
1143
1.42
1177
1.50
—
—
—
—
Table PD-12 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1600
1093
0.92
1126
0.99
1160
1.06
1190
1.13
1222
1.20
1800
1138
1.10
1171
1.17
1203
1.25
1232
1.32
1262
1.39
2000
1182
1.28
1215
1.37
1246
1.46
—
—
—
—
2200
1226
1.48
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
—
—
Table PD-13 — Belt Drive Evaporator Fan Performance — 5 Ton — WSC060A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1
)
1600
707
0.35
774
0.42
837
0.50
898
0.57
953
0.65
1001
0.72
1045
0.80
1087
0.87
1129
0.95
1168
1.03
1800
778
0.48
840
0.56
897
0.64
953
0.72
1008
0.81
1058
0.89
1102
0.98
1143
1.06
1181
1.15
1219
1.23
2000
850
0.65
908
0.73
961
0.81
1012
0.90
1062
1.00
1111
1.09
1157
1.19
1198
1.28
1237
1.37
1274
1.47
2200
923
0.84
978
0.93
1028
1.02
1075
1.12
1120
1.22
1166
1.32
1211
1.43
—
—
—
—
—
—
2400
997
1.07
1049
1.17
1096
1.27
1140
1.37
1183
1.48
—
—
—
—
—
—
—
—
—
—
Table PD-13 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor
1600
1206
1.12
1241
1.20
1275
1.28
1306
1.37
1338
1.46
1800
1256
1.32
1291
1.41
1326
1.50
—
—
—
—
2000
—
—
—
—
—
—
—
—
—
—
2200
—
—
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-20.
Notes:
Data includes pressure drop due to standardfilters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-23 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
For Standard Evaporator Fan Speed (RPM), reference Table PD-20.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-23 to determine additional static pressure drop due to other
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be
necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.