14
PKGP-PRC003-EN
General
Data
(3, 4 Ton)
Table GD-1 — General Data
3 Ton Convertible Units
4 Ton Convertible Units
WSC036A1
WSC036A3,A4,AW
WSC048A1
WSC048A3,A4,AW
Cooling Performance
1
Gross Cooling Capacity
38,100
38,100
50,800
50,800
SEER
2
9.80
10.20
10.50
10.70
Nominal CFM / ARI Rated CFM
1,200 / 1,200
1,200 / 1,200
1,600 / 1,600
1,600 / 1,600
ARI Net Cooling Capacity
36,600
36,000
48,500
48,500
Integrated Part Load Value
—
—
—
—
System Power (KW)
4.09
3.96
5.16
5.05
Heating Performance
1
High Temp. Btuh Rating
35,000
35,000
47,000
47,000
System Power KW
3.46
3.35
4.68
4.53
Low Temp. Btuh Rating
18,600
18,600
28,800
28,800
System Power KW
2.78
2.65
4.14
4.02
HSPF (Btu/Watts-hr)
6.75
6.95
6.80
6.90
Compressor
No./Type
1/Recip.
1/Recip.
1/Scroll
1/Scroll
Outdoor Sound Rating
(dB)
3
82
82
85
85
Outdoor Coil
— Type
Lanced
Lanced
Lanced
Lanced
Tube Size (in.) OD
.3125
.3125
.3125
.3125
Face Area (sq ft)
9.59
9.59
9.59
9.59
Rows/FPI
2/17
2/17
3/17
3/17
Refrigerant Control
Expansion Valve
Expansion Valve
Expansion Valve
Expansion Valve
Indoor Coil
— Type
Lanced
Lanced
Lanced
Lanced
Tube Size (in.)
.3125
.3125
.3125
.3125
Face Area (sq ft)
6.17
6.17
6.68
6.68
Rows/FPI
3/16
3/16
3/16
3/16
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Drain Connection No./Size (in.)
1/¾ NPT
1/¾ NPT
1/¾ NPT
1/¾ NPT
Outdoor Fan
— Type
Propeller
Propeller
Propeller
Propeller
No. Used/Diameter (in.)
1/22
1/22
1/22
1/22
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
Direct/1
CFM
2,950
2,950
3,200
3,200
No. Motors/HP
1/.25
1/.25
1/.40
1/.40
Motor RPM
1,075
1,075
1,075
1,075
Direct Drive Indoor Fan
— Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used
1
1
1
1
Diameter x Width (in.)
10 x 10
10 x 10
11 x 11
11 x 11
Drive Type/No. Speeds
Direct/2
Direct/2
Direct/2
Direct/2
No. Motors
1
1
1
1
Motor HP (Standard/Oversized)
.33/.50
.33/.50
.60/.80
.60/.80
Motor RPM (Low/High Speed)
950/1,060
950/1,060
930/1,000
930/1,000
Oversized Motor RPM (Low/High Speed)
1,100/1,145
1,100/1,145
1,000/1,100
1,000/1,100
Motor Frame Size (Standard/Oversized)
48/48
48/48
48/48
48/48
Belt Drive Indoor Fan
— Type
—
FC Centrifugal
—
FC Centrifugal
No. Used
—
1
—
1
Diameter x Width (in.)
—
11 x 11
—
11 x 11
Drive Type/No. Speeds
—
Belt/Variable Speed
—
Belt/Variable Speed
No. Motors
—
1
—
1
Motor HP (Standard/Oversized)
—
1.00/ —
—
1.00/ —
Motor RPM (Standard/Oversized)
—
1,750/ —
—
1,750/ —
Motor Frame Size (Standard/Oversized)
—
56/ —
—
56/ —
Filters
— Type Furnished
5
Throwaway
Throwaway
Throwaway
Throwaway
(No.) Size Recommended (in.)
(2) 20 x 25 x 1
(2) 20 x 25 x 1
(2) 20 x 25 x 1
(2) 20 x 25 x 1
Refrigerant Charge
(Lbs of R-22)
4
6.5
6.8
9.4
10.2
Notes:
1. Cooling Performance and Heating Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb . Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification
program, which is based on ARI Standard 210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-25.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Optional 2 inch pleated filters are also available.