PKGP-PRC003-EN
41
Electrical
Data
Table ED-4— Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive Indoor Motor
Optional Belt Drive Indoor Motor
To Use
Heater
Heater
Control
Max Fuse Size or
Tons
With
Model No.
KW Rating
1
Stages
MCA
Max Circuit Breaker
2
208/230 Volts Three Phase
BAYHTRR306A
4.5/6.0
1
37.4/39.8
45/45
3
WSC036A3
BAYHTRR312A
9.0/12.0
2
53.0/57.9
60/60
BAYHTRR318A
13.1/17.4
2
67.1/74.1
70/80
BAYHTRR306A
4.5/6.0
1
41.4/43.8
50/50
WSC048A3
BAYHTRR312A
9.0/12.0
2
57.0/61.9
60/70
4
BAYHTRR318A
13.1/17.4
2
71.1/78.1
80/80
BAYHTR306A
4.5/6.0
1
47.0/49.4
60/60
WSC060A3
BAYHTRR312A
9.0/12.0
2
62.6/67.5
70/70
5
BAYHTRR318A
13.1/17.4
2
76.8/83.8
80/90
BAYHTRR323A
17.3/23.0
2
91.4/100.5
100/110
460 Volts Three Phase
BAYHTRR406A
6.0
1
20.3
25
3
WSC036A4
BAYHTRR412A
12.0
2
29.3
30
BAYHTRR418A
17.4
2
37.4
40
BAYHTRR406A
6.0
1
21.9
25
4
WSC048A4
BAYHTRR412A
12.0
2
30.9
35
BAYHTRR418A
17.4
2
39.1
40
BAYHTRR406A
6.0
1
25.2
30
5
WSC060A4
BAYHTRR412A
12.0
2
34.2
40
BAYHTRR418A
17.4
2
42.3
45
BAYHTRR423A
23.0
2
50.8
60
575 Volts Three Phase
BAYHTRRW06A
6.0
1
16.2
20
WSC036AW
BAYHTRRW12A
12.0
2
23.3
25
4
BAYHTRRW18A
17.4
2
29.8
30
BAYHTRRW06A
6.0
1
17.6
20
WSC048AW
BAYHTRRW12A
12.0
2
24.7
25
4
BAYHTRRW18A
17.4
2
31.2
35
BAYHTRRW06A
6.0
1
19.9
20
WSC060AW
BAYHTRRW12A
12.0
2
27.1
30
5
BAYHTRRW18A
17.4
2
33.6
35
BAYHTRRW23A
23.0
2
40.3
45
Notes:
1. Heater kw ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.