PKGP-PRC003-EN
15
General
Data
(5, 6 Ton)
Table GD-2 — General Data
5 Ton Convertible Units
6 Ton Convertible Units
WSC060A1
WSC060A3,A4,AW
WSC072A3,A4,AW
Cooling Performance
1
Gross Cooling Capacity
63,100
63,100
74,000
EER/SEER
2
— /9.70
— /10.10
10.6/ —
Nominal CFM / ARI Rated CFM
2,000/2,000
2,000/2,0000
2,400/2,100
ARI Net Cooling Capacity
60,000
60,000
70,000
Integrated Part Load Value
—
—
—
System Power (KW)
6.90
6.74
6.6
Heating Performance
1
High Temp. Btuh Rating
59,000
59,000
68,000
System Power KW/COP
5.96/ —
5.76/ —
6.04/3.3
Low Temp. Btuh Rating
36,200
36,200
38,000
System Power KW/COP
5.30/ —
5.05/ —
5.06/2.2
HSPF (Btu/Watts-hr)
6.96
7.00
—
Compressor
No./Type
1/Scroll
1/Scroll
1/Scroll
Outdoor Sound Rating
(dB)
3
85
85
90
Outdoor Coil
— Type
Lanced
Lanced
Lanced
Tube Size (in.) OD
.3125
.3125
.3125
Face Area (sq ft)
9.59
9.59
17.00
Rows/FPI
3/17
3/17
2/17
Refrigerant Control
Expansion Valve
Expansion Valve
Expansion Valve
Indoor Coil
— Type
Lanced
Lanced
Lanced
Tube Size (in.)
.3125
.3125
.3125
Face Area (sq ft)
6.68
6.68
9.89
Rows/FPI
3/16
3/16
3/16
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Drain Connection No./Size (in.)
1/¾ NPT
1/¾ NPT
1/¾ NPT
Outdoor Fan
— Type
Propeller
Propeller
Propeller
No. Used/Diameter (in.)
1/22
1/22
1/26
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
CFM
3,200
3,200
6,200
No. Motors/HP
1/.40
1/.40
1/.70
Motor RPM
1,075
1,075
1,075
Direct Drive Indoor Fan
— Type
FC Centrifugal
FC Centrifugal
—
No. Used
1
1
—
Diameter x Width (in.)
11 x 11
5
11 x 11
5
—
Drive Type/No. Speeds
Direct/2
Direct/2
—
No. Motors
1
1
—
Motor HP (Standard/Oversized)
.90/1.00
.90/1.00
—
Motor RPM (Low/High Speed)
985/1,100
985/1,100
—
Oversized Motor RPM (Low/High Speed)
1,080/1,135
1,080/1,135
—
Motor Frame Size (Standard/Oversized)
48/48
48/48
—
Belt Drive Indoor Fan
— Type
—
FC Centrifugal
FC Centrifugal
No. Used
—
1
1
Diameter x Width (in.)
—
11 x 11
12 x 12
Drive Type/No. Speeds
—
Belt/Variable Speed
Belt/Variable Speed
No. Motors
—
1
1
Motor HP (Standard/Oversized)
—
1.00/ —
1.00/2.00
Motor RPM (Standard/Oversized)
—
1,750/ —
1,750/1,750
Motor Frame Size (Standard/Oversized)
—
56/ —
56/56
Filters
— Type Furnished
6
Throwaway
Throwaway
Throwaway
(No.) Size Recommended (in.)
(2) 20 x 25 x 1
(2) 20 x 25 x 1
(4) 16 x 25 x 2
Refrigerant Charge
(Lbs of R-22)
4
7.9
8.5
8.2
Notes:
1. Cooling Performance and Heating Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb . Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification
program, which is based on ARI Standard 210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-25.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5
Fan Diameter with oversized motor is 12 x 11.
6. Optional 2 inch pleated filters are also available.