Trane Mitsubishi Electric NTXMMX20A122A Series Installation Manual Download Page 7

En-6

4-2. GAS CHARGE

Perform gas charge to unit.

1) Connect gas cylinder to the service port of stop valve.

2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air conditioner for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrigerating cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use liquid refrigerant. 

Adding gas refrigerant may change the composition of the refrigerant in the system and affect 

normal operation of the air conditioner. Also, charge the liquid refrigerant slowly, otherwise the 

compressor will be locked.

To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under 

104°F (40°C)) during cold season. But never use naked fire or steam.

Union

Stop valve

Liquid 

pipe

Indoor 

unit

Stop valve with 

service port

Gas 

pipe

Refrigerant gas 

cylinder  

operating valve

(for R410A)

Gauge manifold 

valve (for R410A)

Charge hose 

(for R410A)

Refrigerant gas cylinder for R410A with siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

Union

Union
Union

Model

Indoor unit

NTXMMX20A122A

A

 – 

B

4-3. REMOVING THE MAINTENANCE PANEL

The setting of Dip Switch on the outdoor controller board can be changed 

without removing the front panel.

Follow the procedures below to remove the maintenance panel and set 

the Dip Switch.

1) Remove screw(s) which fix the maintenance panel.

2) Remove the maintenance panel, and perform necessary settings.

3) Install the maintenance panel.

Note:

Make sure to fix the maintenance panel securely. Incomplete installation 

could cause malfunction.

Maintenance panel

4-4. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires cannot be 

detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combination, 

and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.
Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not a mal-

function.

4-5. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, how to 

remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

Procedure

Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the power 

supply.

•  Correction completes in 10 to 15 minutes. When the correction is completed, its result is shown 

by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch (SW871) 

again.

•  When the correction completed without error, do not press the piping/wiring correction switch 

(SW871) again.

When the result is “Not completed”, press the piping/wiring correction switch (SW871) again to 

cancel this function. Then, confirm the wiring and piping combination in a conventional manner by 

operating the indoor units one by one.

•  The operation is done while the power is supplied. Make sure not to contact parts other than 

the switch, including the P.C. board. This may cause electric shock or burn by hot parts and 

live parts around the switch. Contacting the live parts may cause P.C. board damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimination before 

operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED1

(Red)

LED2

(Yellow)

LED3 

(Green)

Lit

Lit

Once

Result of piping/wiring correction function

LED1

(Red)

LED2

(Yellow)

LED3

(Green)

Result

Lit

Not lit

Lit

Completed

(Problem corrected or 

normal)

Once

Once

Once

Not completed 

(Detection failed)

Other indications

Refer to “SAFETY PRE

-

CAUTIONS WHEN LED 

BLINKS” located behind 

the top panel.

VG79A939H01_01En.indd   6

2018/08/03   15:53:02

Summary of Contents for Mitsubishi Electric NTXMMX20A122A Series

Page 1: ...l installation de l appareil ext rieur Lors de l installation de l appareil int rieur consultez la notice d installation de cet appareil Toute alt ration structurelle requise pour l installation doit...

Page 2: ...se parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blockage or loose parts on the power supply plug or the outlet it could cause...

Page 3: ...and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space When installing the unit in an area that is enclosed with walls such as a verandah be sur...

Page 4: ...meter or hard PVC pipe VP16 for drain socket 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 3 ft 1 m away from the TV antenna wire The Q ty for B to K in the abo...

Page 5: ...AWG14 or stranded conductor Min AWG14 Use double insulated copper wire with 600 V insulation Use copper conductors only Follow local electrical code POWER SUPPLY CABLE Use solid or stranded conductor...

Page 6: ...burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the tool se...

Page 7: ...ping correction function This unit has a wiring piping correction function which corrects wiring and piping combination When there is possibility of incorrect wiring and piping combination and confirm...

Page 8: ...manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 1 to 0 psi Gauge 0 05 to 0 MPa or the protection...

Page 9: ...de la fiche d alimentation dans la prise secteur v rifiez qu aucune poussi re salet ni d l ment desserr n est pr sent sur la prise et la fiche Veillez enfoncer fond la fiche d alimentation dans la pr...

Page 10: ...l unit externe Pour viter tout probl me de fonctionnement vitez d installer le climatiseur dans les endroits suivants En pr sence de fuites de gaz inflammable En pr sence d une grande quantit d huile...

Page 11: ...pour l appareil int rieur Apr s le test de contr le des fuites appliquer soigneusement du mat riau isolant pour obstruer les trous Si la tuyauterie doit tre fix e sur un mur contenant des m taux de l...

Page 12: ...ser des conducteurs en cuivre uniquement Respecter le code lectrique local AVERTISSEMENT Utiliser le c ble de connexion conforme aux normes techniques pour raccorder les unit s interne et externe et f...

Page 13: ...l ouverture de service pour recr er les conditions d origine 10 Test de contr le des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile r frig rante G sur les embouts vas s des tuy...

Page 14: ...et de c blage des appareils int rieurs ext rieurs Vous devez donc lancer les essais de fonctionnement l un apr s l autre Concernant le m canisme de protection contre une remise en marche trop rapide...

Page 15: ...de l appareil int rieur pour la m thode d arr t du syst me Si trop de r frig rant a t ajout au syst me de climatisation il se peut que la pression ne parvienne pas baisser jusqu 0 1 0 psi jauge 0 05...

Page 16: ...a toma podr a provocar incendios o descargas el ctricas Si el enchufe de alimentaci n presenta piezas sueltas sustit yalo Fije firmemente la cubierta de la instalaci n el ctrica a la unidad interior y...

Page 17: ...el lado de salida de aire de la unidad exterior Para instalar el aparato de aire acondicionado evite los lugares siguientes donde es m s probable que ocurran problemas Donde pueda haber una fuga de ga...

Page 18: ...3 15 16 pulg 100 mm M s de 7 7 8 pulg 200 mm si hay obst culos a ambos lados Despu s de la prueba de fugas aplique material aislante de modo que no queden huecos Cuando los tubos deban instalarse en...

Page 19: ...de cobre Siga la normativa el ctrica local ATENCI N Conecte las unidades interior y exterior con el cable de conexi n norma lizado destinado a este fin y sujete bien el cable al panel de terminales de...

Page 20: ...pa de la abertura de servicio de la v lvula de retenci n situada en el lado de la tuber a de gas de la unidad exterior Inicialmente las v lvulas de retenci n est n completamente cerradas y cubiertas c...

Page 21: ...ger el acondicionador de aire Funci n de correcci n de conexiones tuber as Esta unidad tiene una funci n de correcci n de conexiones tuber as que corrige la combinaci n de las mismas Cuando exista la...

Page 22: ...te el manual de instalaci n de la unidad interior para m s detalles acerca del m todo de detenci n de la operaci n Si se ha a adido demasiado refrigerante al sistema con acondicionador de aire puede q...

Page 23: ...A4_white_tombo indd 1 2016 04 25 10 16 47...

Page 24: ...G79A939H01 HEAD OFFICE 1340 SATELLITE BOULEVARD SUWANEE GA 30024 USA MITSUBISHI ELECTRIC TRANE HVAC US LLC VG79A939H01_cover4 indd 2 2018 08 03 11 27 51 Publication No DL SVN035A XX Published Dec 2018...

Reviews: