Trane Mitsubishi Electric NTXMMX20A122A Series Installation Manual Download Page 5

En-4

2-2. CONNECTING  WIRES FOR OUTDOOR UNIT

•  Be sure to use special circuits for room air conditioner.

•  Wiring work should be based on applicable technical standards.

•  Wiring connections should be made following the diagram.

•  Screws should be tightened so they won’t loosen.

ELECTRICAL SPECIFICATIONS

OUTDOOR UNIT

NTXMMX20A122A

Power supply  

(V, PHASE, Hz)

208/230, 1, 60

Max. Fuse size 

(time delay) (A)

20

Min. Circuit 

Ampacity (A)

17.2

Fan motor 

(F.L.A)

1.77

Com-

pressor

(R.L.A)

10.7

(L.R.A)

15.5

Control voltage

Indoor unit-Remote controller : (Wireless)

Indoor unit-Outdoor unit : DC 12-24 V

1-3/8 in.

(35 mm)

5/8 in.

(15 mm)

Lead wire

1) Remove the service panel.

2) Remove the conduit plate.

3) Attach the conduit connector to conduit plate with lock nut then secure 

it to the unit with screws. Be sure to attach the conduit connectors in 

the correct locations according to their sizes.

4) Connect ground wires to the TB bed.

5) Loosen terminal screw, and connect indoor/outdoor unit connecting 

wire (B) from the indoor unit correctly on the terminal block. Be careful 

not to make mis-wiring. Fix the wire to the terminal block securely so 

that no part of its core is appeared, and no external force is conveyed 

to the connecting section of the terminal block. 

6) Firmly tighten the terminal screws to prevent them from loosening. After 

tightening, pull the wires lightly to confirm that they do not move.

7) Perform 5) and 6) for each indoor unit.

8) Connect power supply cord (A).

9) Close the service panel securely. Make sure that 3-2. PIPE CONNEC

-

TION is completed.

CONNECTING WIRES AND CONNECTING GROUND WIRE

•  Use solid conductor Min. AWG14 or stranded conductor Min. AWG14.

•  Use double insulated copper wire with 600 V insulation.

•  Use copper conductors only.

Follow local electrical code.

POWER SUPPLY CABLE

•  Use solid or stranded conductor Min. AWG8.

•  Use copper conductors only.

Follow local electrical code.

GROUND WIRE

•  Use solid or stranded conductor Min. AWG8.

•  Use copper conductors only.

Follow local electrical code.

 WARNING:

•  Use the indoor/outdoor unit connecting wire that meets the Stand-

ards to connect the indoor and outdoor units and fix the wire to 

the terminal block securely so that no external force is conveyed 

to the connecting section of the terminal block. An incomplete 

connection or fixing of the wire could result in a fire.

Remark:

*  Use a ring tongue terminal in order to connect a ground wire to terminal.

•  Connect wires to the matching numbers of terminals.

•  Be sure to attach each screw to its correspondent terminal when 

securing the cord and/or the wire to the terminal block.

Terminal block

Grounding 

terminal *

208/230 V AC

1 phase 60 Hz

Grounding 

terminal *

Terminal block

Ground

OUTDOOR UNIT

Power supply

208/230 V AC 

1 phase 2 wires 60 Hz

Disconnect 

switch

Grounding 

terminal *

Terminal block

Terminal block

Terminal block

For future servicing, give extra length to the connecting wires.

Conduit connector

Trade size of conduit

(a) Power supply

3/4 in.

(b) Indoor/outdoor

1/2 in.

INDOOR UNIT

Note:

•  Removing the handle increases the effectiveness of the wiring operation.

•  Be sure to reinstall the handle.

•  Turn on the main power when the ambient temperature is -4°F 

(-20°C) or higher.

•  Under conditions of -4°F (-20°C), it needs at least 4hr stand by 

before the units operate in order to warm the electrical parts.

Service panel

Screws

Lock nut

Conduit connector

Conduit plate

Screw

VG79A939H01_01En.indd   4

2018/08/03   15:53:02

Summary of Contents for Mitsubishi Electric NTXMMX20A122A Series

Page 1: ...l installation de l appareil ext rieur Lors de l installation de l appareil int rieur consultez la notice d installation de cet appareil Toute alt ration structurelle requise pour l installation doit...

Page 2: ...se parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blockage or loose parts on the power supply plug or the outlet it could cause...

Page 3: ...and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space When installing the unit in an area that is enclosed with walls such as a verandah be sur...

Page 4: ...meter or hard PVC pipe VP16 for drain socket 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 3 ft 1 m away from the TV antenna wire The Q ty for B to K in the abo...

Page 5: ...AWG14 or stranded conductor Min AWG14 Use double insulated copper wire with 600 V insulation Use copper conductors only Follow local electrical code POWER SUPPLY CABLE Use solid or stranded conductor...

Page 6: ...burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the tool se...

Page 7: ...ping correction function This unit has a wiring piping correction function which corrects wiring and piping combination When there is possibility of incorrect wiring and piping combination and confirm...

Page 8: ...manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 1 to 0 psi Gauge 0 05 to 0 MPa or the protection...

Page 9: ...de la fiche d alimentation dans la prise secteur v rifiez qu aucune poussi re salet ni d l ment desserr n est pr sent sur la prise et la fiche Veillez enfoncer fond la fiche d alimentation dans la pr...

Page 10: ...l unit externe Pour viter tout probl me de fonctionnement vitez d installer le climatiseur dans les endroits suivants En pr sence de fuites de gaz inflammable En pr sence d une grande quantit d huile...

Page 11: ...pour l appareil int rieur Apr s le test de contr le des fuites appliquer soigneusement du mat riau isolant pour obstruer les trous Si la tuyauterie doit tre fix e sur un mur contenant des m taux de l...

Page 12: ...ser des conducteurs en cuivre uniquement Respecter le code lectrique local AVERTISSEMENT Utiliser le c ble de connexion conforme aux normes techniques pour raccorder les unit s interne et externe et f...

Page 13: ...l ouverture de service pour recr er les conditions d origine 10 Test de contr le des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile r frig rante G sur les embouts vas s des tuy...

Page 14: ...et de c blage des appareils int rieurs ext rieurs Vous devez donc lancer les essais de fonctionnement l un apr s l autre Concernant le m canisme de protection contre une remise en marche trop rapide...

Page 15: ...de l appareil int rieur pour la m thode d arr t du syst me Si trop de r frig rant a t ajout au syst me de climatisation il se peut que la pression ne parvienne pas baisser jusqu 0 1 0 psi jauge 0 05...

Page 16: ...a toma podr a provocar incendios o descargas el ctricas Si el enchufe de alimentaci n presenta piezas sueltas sustit yalo Fije firmemente la cubierta de la instalaci n el ctrica a la unidad interior y...

Page 17: ...el lado de salida de aire de la unidad exterior Para instalar el aparato de aire acondicionado evite los lugares siguientes donde es m s probable que ocurran problemas Donde pueda haber una fuga de ga...

Page 18: ...3 15 16 pulg 100 mm M s de 7 7 8 pulg 200 mm si hay obst culos a ambos lados Despu s de la prueba de fugas aplique material aislante de modo que no queden huecos Cuando los tubos deban instalarse en...

Page 19: ...de cobre Siga la normativa el ctrica local ATENCI N Conecte las unidades interior y exterior con el cable de conexi n norma lizado destinado a este fin y sujete bien el cable al panel de terminales de...

Page 20: ...pa de la abertura de servicio de la v lvula de retenci n situada en el lado de la tuber a de gas de la unidad exterior Inicialmente las v lvulas de retenci n est n completamente cerradas y cubiertas c...

Page 21: ...ger el acondicionador de aire Funci n de correcci n de conexiones tuber as Esta unidad tiene una funci n de correcci n de conexiones tuber as que corrige la combinaci n de las mismas Cuando exista la...

Page 22: ...te el manual de instalaci n de la unidad interior para m s detalles acerca del m todo de detenci n de la operaci n Si se ha a adido demasiado refrigerante al sistema con acondicionador de aire puede q...

Page 23: ...A4_white_tombo indd 1 2016 04 25 10 16 47...

Page 24: ...G79A939H01 HEAD OFFICE 1340 SATELLITE BOULEVARD SUWANEE GA 30024 USA MITSUBISHI ELECTRIC TRANE HVAC US LLC VG79A939H01_cover4 indd 2 2018 08 03 11 27 51 Publication No DL SVN035A XX Published Dec 2018...

Reviews: