148
RT-SVX072A-EN
Table 71.
Relief/return fan VFD parameters
Menu
ID
Description
Parameter Setting
Operation
Display
0-01
Language
[0] English US
0-03
Regional Settings
[1] North American
0-06
Grid Type
Set to applicable unit power supply
[102] 200-240V/60Hz for 208 & 230V/60Hz units
[122] 440-480V/60Hz for 460V/60Hz units
[132] 525-600V/60Hz for 575V/60Hz units
[12] 380-440v/50Hz for 380 & 415V/50Hz supply
For IT Grid (no ground connections) or Corner grounded Delta power supply systems,
the applicable voltage/Hz and IT-Grid or Delta should be selected.
0-40
[Hand on] - Key on
LCP
[0] Disabled
Load and Motor
1-20
Motor Power (KW/HP)
Per Motor Nameplate HP - KW
1-22
Motor Voltage (V)
Per Motor Nameplate Voltage
1-23
Motor Frequency (HZ)
Per Motor Nameplate Frequency
1-24
Motor Current (A)
Per Motor Nameplate FLA
1-25
Motor Nominal Speed
(RPM)
Per Motor Nameplate Rated Speed
1-73
Flying Start
[1] Enabled
1-90
Motor Thermal
Protection
[4] ETR Trip1
Brakes
2-00
DC Hold / Preheat
Current (%)
[0] 0%
2-01
DC Brake Current (%)
[0] 0%
2-04
DC Brake Cut In
Speed
[10] 10 Hz
Reference /
Ramps
3-02
Minimum Reference
(HZ)
[22] 22 Hz
3-03
Maximum Reference
(HZ)
[60] 60 Hz
3-15
Reference 1 Source
[11] Local bus reference
3-16
Reference 2 Source
[0] No function
3-17
Reference 3 Source
[0] No function
3-41
Ramp 1 Ramp up
Time (S)
[30] 30s
3-42
Ramp 1 Ramp down
Time (S)
[30] 30s
Limits /
Warnings
4-10
Motor Speed Direction
[0] Clockwise
4-12
Motor Speed Low
Limit [HZ]
[22] 22 Hz
4-14
Motor Speed High
Limit (Hz)
[60] 60 Hz
4-18
Current Limit (%)
[100] 100%
4-19
Max Output
Frequency (Hz)
[60] 60 Hz