RT-SVX072A-EN
95
Table
35.
Component
static
pressure
drops
(in.
W.G.),
20
to
75
tons
air-cooled
(continued)
CFM
Std
Evap
Coil
Heating
System
Filters
Std
Roof
Econ
w/
or
w/
out
Re-
lief
HGR-
H
Dry
Wet
SFH_
-
FC
SFH_
-
DDP
SHE_
SLH_
SSH_
Throwaway
Perm
Wire
Bag
&
Pre
Cart
&
Pre
Final
Cart
Low
High
Low
High
All
kW
Low
High
Low
High
Std
High
27000
1.01
1.26
0.51
0.33
1.05
0.88
0.30
0.42
0.52
0.30
0.48
0.17
0.17
0.06
1.12
1.26
0.98
0.27
0.28
0.16
Notes:
1
.
Static
pressure
drops
of
accessory
components
must
be
added
to
external
static
pressure
to
enter
fan
selection
tables.
2
.
Gas
heat
section
maximum
temperature
rise
of
60°
F.
3
.
Throwaway
filter
option
limited
to
300
ft/min
face
velocity
.
4
.
Bag
filter
option
limited
to
740
ft/min
face
velocity
.
5
.
Horizontal
roof
curbs
assume
0.50"
static
pressure
drop
or
double
the
standard
roof
curb
pressure
drop,
whichever
is
greater
.
6
.
No
additional
pressure
loss
for
model
SXH_.
7
.
F
or
final
filters
w/
prefilters
(digit
13
=
M,
N,
P,
Q)
also
add
pressure
drop
for
throwaway
filter
.