Minimum Required Clearance
Figure 9. Minimum operation and service clearances for single and multiple unit installation
8'0" MINIMUM
SERVICE / AIRFLOW
CLEARANCE
8'0" MINIMUM
SERVICE / AIRFLOW
CLEARANCE
8'0" MINIMUM
SERVICE / AIRFLOW
CLEARANCE
6'0" MINIMUM
SERVICE / AIRFLOW
CLEARANCE
(SEE NOTE 4)
C
D
(NOTE 1)
NOT TO SCALE
A
B
E
K
F
H
G
G
L
F
H
G / J
J
L
M
N
P
MULTIPLE UNIT INSTALLATION
12'0" MINIMUM
SERVICE / AIRFLOW
CLEARANCE
(NOTE 3)
16'0" MINIMUM
SERVICE / AIRFLOW
CLEARANCE
(NOTE 3)
CONDENSER
SECTION
(NOTE 1)
FRESH AIR
INTAKE
EXHAUST AIR
CONDENSER
SECTION
(NOTE 1)
FRESH AIR
INTAKE
EXHAUST AIR
CONDENSER
SECTION
(NOTE 1)
FRESH AIR
INTAKE
EXHAUST AIR
Return Air Opening
Outside Air Intake
Supply Air Opening
Condenser Section
Optional 2’10-3/4” Exhaust/Return Access Door (180° swing)
Hinged 2’10-3/4” Filter Access Door (180° swing)
Hinged 2’10-3/4” optional Heater or Final Filter Access Door (180° swing)
Hinged 2’10-3/4” Supply Fan Access Door (180° swing) (90-130 ton)
Hinged 2’4-1/2” Control Panel Door (180° swing) (90-130 ton)
Hinged 2’10-3/4” VFD Access Door (180° swing)
Hinged 2’10-3/4” Evap Condenser Access Door (180° swing)
Hinged 2’8” Control Panel Door (180° swing) (20-36 ton)
Hinged 3’6” Control Panel Door (180° swing) (40-75 ton)
A
B
C
D
E
F
G
H
J
K
L
M
=
=
=
=
=
=
=
=
=
=
=
=
Single Unit Installation
Legend