RLC-SVX19E-GB
78
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Note for installation
The maximum pressure of the Glycol side when unit is equipped with free cooling is 400 kPa for Glycol free option
or 600kPa for Direct free cooling except on evaporator side for glycol free 1000 kPa Refer to unit nameplate for rated
value.
Pump operation with Glycol free : it is requested to have a minimum water side pressure of 250 kPa to avoid
cavitation.
Glycol free option : To avoid component damage, a filter (1 mm mesh) must be supplied by the customer and
installed at the unit inlet.
All Free-cooling units must be freeze-protected with at least 30% Ethylene Glycol in the cooling loop circuit which is
the most convenient percentage in order to protect the unit against freezing.
Protection coverage with 30% Ethylene Glycol:
- Freezing point without burst effect = -13°C
- Freezing point with burst effect = -50°C.
Water can be trapped in BPHE and specific care must be taken to remove it completly from BPHE during off mode.
IMPORTANT – WATER QUALITY
Glycol or brine must be carefully chosen with the help of a reputable water treatment specialist. The additional
materials to the evaporator circuit are made with Carbon Steel, Copper, Zinc, Synthetic rubber, Aluminum AA3102,
AA3003, and AA4045. Water should be free from foreign solid particules.
All Submittal, lifting diagram, neoprene pads positioning and wiring diagrams have been supplied with chiller order.
Free cooler by-pass valve adjustment
For intervention on free cooler by-pass valve it is recommended to consult the valve service literature.
For every new referencing of the motor end travel, an adaptation of the motor should be done by pushing button 2
To change the bypass percentage follows below procedure:
− No tuning is needed on free cooling valve which always stays on full opening/closure.
− For bypass valve Belimo, minimum opening can be adjusted by pushing the release button (4) and by
turning handle 5 to 50% opening for instance (45°)
Optional Free-Cooling