RLC-SVX19E-GB
100
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Table 34 – RTAF 350 SE/HSS/HE/XE/HSE
SIZE
RTAF 350 SE/HE/XE/HSS/HSE
EVAP
500D
Min Coolant Flow (m
3
/h)
AWT (°C)
%Wt Mono Propylene Glycol
20%
25%
30%
35%
40%
4
49
58
71
87
107
2
54
65
78
96
119
0
61
72
87
107
133
-2
68
81
98
120
149
-4
78
91
110
135
169
-6
89
104
125
153
192
-8
120
143
175
219
-10
165
201
251
-12
192
233
290
AWT (°C)
%Wt Ethylene Glycol
20%
25%
30%
35%
40%
4
37
43
49
57
65
2
40
46
53
61
71
0
43
50
58
66
77
-2
47
54
62
72
84
-4
51
59
68
79
92
-6
55
64
74
86
100
-8
60
70
81
95
110
-10
76
89
104
122
-12
98
115
135
Table 35 – RTAF 380 SE/HSS/HE/XE/HSE
SIZE
RTAF 380 SE/HE/XE/HSS/HSE
EVAP
500C
Min Coolant Flow (m
3
/h)
AWT (°C)
%Wt Mono Propylene Glycol
20%
25%
30%
35%
40%
4
54
65
79
96
119
2
60
72
87
107
132
0
67
80
97
119
148
-2
76
90
108
133
166
-4
86
102
122
150
187
-6
99
116
139
170
213
-8
133
159
194
243
-10
183
223
279
-12
213
259
322
AWT (°C)
%Wt Ethylene Glycol
20%
25%
30%
35%
40%
4
41
48
55
63
72
2
45
51
59
68
78
0
48
55
64
74
85
-2
52
60
69
80
93
-4
56
65
75
88
102
-6
61
71
82
96
111
-8
67
77
90
105
123
-10
85
99
116
135
-12
109
127
150
AWT: Average Water Temperature which is the average of Leaving Water Temperature and Entering Water Temperature.
Evaporator Waterside