Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
General Electrical Recommendations
Electrical Parts
When reviewing this manual keep in mind.
•
All field-installed wiring must be in accordance with
local regulations, CE directives and guidelines. Be sure
to satisfy proper equipment grounding requirements
according CE
•
The following standardized values - Maximum Amps -
Short Circuit Amps - Starting Amps are displayed on unit
nameplate.
•
All field-installed wiring must be checked for proper
terminations, and for possible shorts or grounds.
Note:
always refer to wiring diagrams shipped with chiller
or unit submittal for specific electrical schematic and
connection information.
Important:
to prevent control malfunctions, do not run
low voltage wiring (<30V) in conduit with conductors
carrying more than 30 volts.
WARNING! Hazardous Voltage with Capacitor!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run and
AFD (Adaptive Frequency TM Drive) capacitors before
servicing. Follow proper lockout/tagout procedures to
ensure the power cannot be inadvertently energized.
•
For variable frequency drives or other energy storing
components provided by Trane or others, refer to the
appropriate manufacturer’s literature for allowable
waiting periods for discharges capacitors. Verify with an
appropriate voltmeter that all capacitors have discharged
•
DC bus capacitors retain hazardous voltages after input
power has been disconnected. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized
After disconnecting input power, wait five (5) minutes for
units which are equipped with EC fans and wait twenty
(20) minutes for units which are equipped with variable
frequency drive (0V DC) before touching any internal
components.
Failure to follow these instructions could result death or
serious injury
For additional information regarding the safe discharge
of capacitors, see “Adaptive Frequency™ Drive (AFD3)
Capacitor Discharge” and BAS-SVX19B-E4.
Hazardous Voltage – Pressurized Burning Fluid!
Before removing compressor terminal box cover for
servicing, or servicing power side of control panel,
CLOSE COMPRESSOR DISCHARGE SERVICE VALVE
and disconnect all electric power including remote
disconnects. Discharge all motor start/run capacitors.
Follow lockout/tagout procedures to ensure the power
cannot be inadvertently energized. Verify with an
appropriate voltmeter that all capacitors have discharged.
The compressor contains hot, pressurized refrigerant.
Motor terminals act as a seal against this refrigerant.
Care should be taken when servicing NOT to damage or
loosen motor terminals.
Do not operate compressor without terminal box cover
in place.
Failure to follow all electrical safety precautions could
result in death or seriously injure.
CAUTION!
To avoid corrosion, overheating or general
damage, at terminal connections, unit is designed for
copper mono-conductors only. In case of multiconductor
cable, an intermediate connection box must be
added. For cable with alternative material, bi-material
connecting devices are mandatory. Cable routing inside
control panel should be made case by case by installer.
Do not allow conduit to interfere with other components,
structural members or equipment. Control voltage
(115V) wiring in conduit must be separate from conduit
carrying low voltage (<30V) wiring. To prevent control
malfunctions, do not run low voltage wiring (<30V) in
conduit with conductors carrying more than 30V.
WARNING!
The Warning Label shown in Figure 19 is displayed on
the equipment and shown on wiring diagrams and
schematics. Strict adherence to these warnings must be
observed. Failure to do so may result in personal injury
or death.
CAUTION!
Units must not be linked to the neutral
wiring of the installation. Units are compatible with the
following neutral operating conditions:
* Differential protection should be suited for industrial
machinery with current leak which can be higher than
500 mA (several motors and frequency drives).
TNS
IT
TNC
TT
Standard
Special
Special
Standard*