RLC-SVX19E-GB
22
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
General Data
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
090
105
125
145
155
175
190
205
245 (9)
Low ambient fan option
Fan / motor Type
Propeller fan / Variable speed - EC motor
Airflow per Fan
(m3/h)
20000
20000
20000
20000
20000
20000
20000
20000
20000
Max Power input per Motor
(kW)
1.95
1.95
1.95
1.95
1.95
1.95
1.95
1.95
1.95
Max Amps per Motor
(A)
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
Motor RPM
(rpm)
910
910
910
910
910
910
910
910
910
System data (4)
Nb of refrigerant circuit
#
2
2
2
2
2
2
2
2
2
Minimum cooling load % (6)
%
15
15
15
15
15
15
15
15
15
Standard unit
R134a/R513A refrigerant charge Circuit1 / Circuit 2 (4)
(kg)
41 / 39
40 / 38
42 / 38
45 / 43
47 / 41
57 / 43
59 / 53
63 / 59
63 / 59
Oil charge Circuit 1 / Circuit 2 (7)
(l)
6 / 6
6 / 6
6 / 6
6 / 6
7 / 6
7 / 6
7 / 7
8 / 8
8 / 8
POE Oil type
OIL00317 or OIL00311
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(6) Max speed - range is 60% to 100% of max speed.
(7) Refrigerant charge may vary according to option - for in20% for process (digit 19=P). For real value refer to unit nameplate.
(8) Data containing information on two circuits shown as follows: ckt1/ckt2.
(9) 245 HSS is available in low and standard ambient (not available in high ambient).
Table 8 – General Data RTAF 090 - 245 High Seasonal Efficiency short - Standard and Low Noise (continued)