RLC-SVX19E-GB
15
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
General Data
Table 5 – General Data RTAF 090 - 205 Extra Efficiency - Extra Low Noise
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
090
105
125
145
155
175
190
205
Cooling Capacity (1)
(kW)
326
380
447
526
569
633
689
752
Unit electrical data (2) (3) (5)
Maximum Power input in cooling
(kW)
141.1
162.3
190.5
222.6
245.0
267.9
294.2
317.1
Unit rated amps (Max compr +Fan+Control)
(A)
227
265
315
371
406
445
486
525
Unit start up amps (Starting Amps of the largest
compr+RLA of 2nd compr+RLA of all fans+ control)
(A)
274
329
440
496
559
570
639
639
Unit Power factor
0.90
0.89
0.88
0.87
0.87
0.87
0.88
0.87
Max power cable cross section
(mm²)
240
240
240
2*300
2*300
2*300
2*300
2*300
Disconnect switch size
(A)
400
400
500
630
630
630
800
800
Compressor
Quantity
#
2
2
2
2
2
2
2
2
Type
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Model (11)
45/45
50/50
70/50
70/70
85/70
100/70
100/85
100/100
Max Compr Power input Circuit 1/Circuit 2
kW
60/60
71/71
99/71
99/99
121/99
144/99
144/121
144/144
Max Amps Circuit1 / Circuit 2 (3) (5)
(A)
97/97
116/116
166/116
166/166
201/166
240/166
240/201
240/240
Start up Amps Circuit1 / Circuit 2 (3) (5)
(A)
144/144
180/180
291/180
291/291
354/291
354/291
354/354
354/354
Motor RPM
(rpm)
3000
3000
3000
3000
3000
3000
3000
3000
Oil sump heater Circuit1 / Circuit 2
(W)
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
Evaporator
Quantity
#
1
1
1
1
1
1
1
1
Type
Flooded shell and tube heat exchanger
Evaporator model
115B
115A
165B
165B
165A
200B
200B
250B
Evaporator Water Content volume
(l)
51
58
74
74
78
99
99
118
Antifreeze Heater
(W)
1640
1640
1640
1640
1640
2040
2040
2040
Two pass evaporator
Evap. Water Flow rate - Minimum
(l/s)
8.0
9.4
11.6
11.6
12.4
14.2
14.2
17.9
Evap. Water Flow rate - Maximum (6)
(l/s)
29.6
34.7
43.1
43.1
46.0
52.6
52.6
66.5
Nominal water connection size (Grooved coupling)
(in) -
(DN)
4" - 100
4" - 100
5" - 125
5" - 125
5" - 125
6" - 150
6" - 150
6" - 150
Two pass with turbulator evaporator
Evap. Water Flow rate - Minimum (6)
(l/s)
6.6
7.8
9.7
9.7
10.3
11.8
11.8
14.9
Evap. Water Flow rate - Maximum
(l/s)
26.6
31.2
38.7
38.7
41.3
47.2
47.2
59.7
Nominal water connection size (Grooved coupling)
(in) -
(mm)
4" - 100
4" - 100
5" - 125
5" - 125
5" - 125
6" - 150
6" - 150
6" - 150
Hydraulic Module Components
Standard head pressure pump option
Available Head Pressure (1)
(kPa)
142
128
143
122
179
172
153
149
Max Motor Power input
(kW)
5.5
5.5
7.5
7.5
11.0
11.0
11.0
11.0
Max Amps
(A)
11.0
11.0
14.4
14.4
20.8
20.8
20.8
20.8
High head pressure pump option
Available Head Pressure (1)
(kPa)
253
240
224
245
237
230
264
260
Max Motor Power input
(kW)
11.0
11.0
11.0
15.0
15.0
15.0
18.5
18.5
Max Amps
(A)
20.8
20.8
20.8
28.0
28.0
28.0
34.5
34.5
Expansion Tank Volume
(l)
80
80
80
80
80
80
80
80
Max User water loop Volume for factory mounted
expansion tank (1)
(l)
6000
6000
6000
6000
6000
6000
6000
6000
Max. Water-side Operating Pressure without pump
package
(kPa)
1000
1000
1000
1000
1000
1000
1000
1000
Max. Water-side Operating Pressure with pump package
(kPa)
450
450
450
450
450
450
450
450
Antifreeze Heater with pump package
(W)
840
840
840
840
840
840
840
840
Condenser
Type
Full aluminum Micro channel heat exchanger
Quantity
#
5/5
5/5
5/5
6/6
6/6
7/5
7/7
7/7
Face area per coil
(m²)
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
Condenser Fan
Quantity
#
5/5
5/5
5/5
6/6
6/6
7/5
7/7
7/7
Diameter
(mm)
800
800
800
800
800
800
800
800
Standard / High ambient fan option
Fan / motor Type
Propeller fan / Variable speed - EC motor
Airflow per Fan
(m3/h)
15000
17400
17400
17400
17400
20000
20000
20000
Max Power input per Motor
(kW)
1.95
1.95
1.95
1.95
1.95
1.95
1.95
1.95
Max Amps per Motor
(A)
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
Motor RPM
(rpm)
660
760
760
760
760
860
860
860