RLC-SVX19E-GB
51
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Chilled Water Piping Recommendations
Drainage
A large capacity drain must be provided for water vessel
drain-down during shutdown or repair. The evaporator is
provided with drain connections. An air vent on top of the
evaporator water box prevents vacuum by removing air
from evaporator for complete drainage.
Water Treatment
In the evaporator the following material are in contact
with water:
•
Water boxes are made of cast iron (GJL250 EN-code)
•
Tube plates are made of steel (P265GH code)
•
Tubes are made of copper
•
Turbulators when present in evaporator tubes are made
of phosphorous brass.
When the unit is supplied with hydraulic module, the
following additional materials are in contact with water:
•
Pump frame and connections are made of cast iron
•
Water pipes are made of iron
•
Pipe sealings are made of EPDM rubber (ethylene
propylene diene monomer rubber)
•
Pump sealings are made of silicon carbide
•
Strainer is made of stainless steel
Dirt, scale, products of corrosion, and other foreign
material will adversely affect heat transfer between the
water and system components. Foreign matter in the
chilled-water system can also increase pressure drop and
consequently, reduce water flow. Proper water treatment
must be determined locally, depending on the type of
system and local water characteristics.
Neither salt nor brackish water is recommended for use
in Trane air-cooled chillers. Use of either will lead to an
unpredictably shorter life cycle. Trane encourages the
employment of a reputable water treatment specialist,
familiar with local water conditions, to assist in this
determination and in the establishment of a proper water
treatment program.
CAUTION!
If using an acidic commercial flushing
solution, construct a temporary bypass around the
unit to prevent damage to internal components of
the evaporator. Trane assumes no responsibility for
equipment failures which results from untreated or
improperly treated water or saline or brackish water.
If calcium chloride is used for water treatment, an
applicable corrosion inhibitor must also be used. Failure
to do so may result in damage to system components. Do
not use untreated or improperly treated water. Equipment
damage may occur.