Compressor Starts and Running Time
The starts and hours counters are displayed as follows:
Compressor Starts:
XXXXX
Compressor Running Time
Hrs:Min:Sec
Discharge Oil Pressure, Oil Tank Pressure
This screen is only displayed if the “Oil Pressure Protection” setpoint is
set to “Transducer” or “Xducer & Switch”. Suppress this screen for
FastPak or CVGF.
Discharge Oil Pressure:
XXX.X psig
Oil Tank Pressure:
XXX.X psig
Note:
This screen was modified with first FastPak release dated
(11/4/96).
Differential Oil Pressure, Oil Temperature
Differential Oil Pressure:
XXX.X [units]
Oil Tank Temperature:
XXX.X F/C
For CVHE/F/G/B, Differential Oil Pressure: xxx.x [units] is only displayed
if the “Oil Pressure Protection” setpoint is set to “Transducer” or “Xducer
& Switch”. If Switch is selected as the setpoint, then Differential Oil
Pressure Switch: [status] is displayed where Status is open or closed.
For FastPak Differential Oil Pressure: xxx.x [units] is only displayed if the
“Oil Pressure Protection Setpoint” is set to “Diff Xducer” if Switch is
selected as the setpoint, then Differential Oil Pressure Switch: [Status] is
displayed where Status is open or closed.
Note:
This screen was modified with first FastPak release dated
(11/4/96).
The possible value for [units] is “psid” or “kPa” dependent upon whether
English or SI units are selected.
Bearing Temperatures #1 and #2
The following will be displayed only if the Bearing Temp Sensors Option
is installed.
Bearing Temperature 1:
XXX.X F/C
Bearing Temperature 2:
XXX.X F/C
CVRC-M-1D
29
Chiller Report