The Refrigerant Monitor Calibration password is
Enter for the field calibration menu. If a refrigerant monitor calibration
password is entered, the display goes to the menu items defined below.
If a key is not pressed every 20 minutes in this pass- word protected
menu, the display returns to the Chiller Operating Mode display of the
Chiller Report, and a refrigerant monitor calibration password must be
entered and again to return to this menu.
Refrigerant Monitor Settings Group Heading
This header is displayed if the field calibration password was entered.
Refrigerant Monitor Field Calibration Group:
Press (Next) (Previous) To Continue
Refrigerant Monitor Mode
This item is displayed if the Channel Scanner is installed.
Refrigerant Monitor Mode:
[Mode]
[Active Channel]
XXXX PPM[Rfgt Type]
This item is displayed if the Channel Scanner is not installed.
Refrigerant Monitor Mode:
[Mode]
XXXX PPM[Rfgt Type]
Refrigerant Zero Calibration
Refrigerant Zero Calibration:
(Enter) to Start, (Next) to Continue
If Next is pressed the following refrigerant zero calibration screens are
skipped. If Enter is pressed the following screens are displayed to permit
refrigerant zero calibration.
Starting The Calibration Procedure:
Please Wait
If the refrigerant monitor is unable to calibrate, the following item shall be
displayed.
Unable to Calibrate
Otherwise, continue with the following screens.
Connect Refrigerant Zero Gas
(Next) To Continue, (Cancel) To Exit
Open Gas Sample Valve
(Next) To Continue, (Cancel) To Exit
XXXX PPM[RfgtType]
(Enter) To Adjust Conc.,• (Cancel) To Exit
Locking The Reading
Please Wait
CVRC-M-1D
81
Refrigerant Monitor Calibration
-
-
-