AF Re-Optimization Timer Time Remaining
The following will be displayed only if the Starter Type is Adaptive
Frequency and Adaptive Speed Control Algorithm is Enabled.
The purpose of this report is to limit the time the unit operates at or near
surge. The machine learns the curve and rides the surge line.
AF Re-Optimization Time Remaining:
X.XX Hrs
Press (+) (-) to Change Setting
Note:
This is a Report only for Trouble-shooting purposes.
Inlet Guide Vane Position
The following screen will be suppressed if “Inlet Guide Vane Output” is
set to “Pulsed”.
Inlet Guide Vane Position:
XXX.X Open
Inlet Guide Vane Position:
XX.X Degrees
Compressor Line Currents RLA
The following screen will be suppressed if FastPak Starter Type is set to
Stand Alone - No Starter Module.
Compressor Line Currents - % RLA
A XXX.X%
B XXXX.X%
CXXXX.X%
Compressor Line Currents Amps
The following screen will be suppressed if FastPak Starter Type is set to
Stand Alone - No Starter Module.
Compressor Line Currents - Amps
A XXX.X
B XXXX.X
CXXXX.X
Compressor Line Voltages
The following will be displayed only if the Line Voltage Sensing Option is
installed.
Compressor Line Voltages
AB XXXXv
BCXXXXv
CA XXXXv
CVRC-M-1D
39
Report