CVRC-M-1D
97
Diagnostics Menu
Diagnostic Codes
As shown below, a “LATCHING” diagnostic is a condition which
causes the machine or a portion of the machine as noted to shut down
and requires a manual reset to restore operation. A diagnostic that is
non-latching resets automatically when the condition causing the
diagnostic goes away. A non-latching diagnostic shuts down the
machine or a part of the machine if so indicated. If a diagnostic is
informative only, no machine or circuit action is taken except to load a
diagnostic code into the last diagnostic register.
Unless otherwise stated, all active diagnostics will be lost on loss of
power.
DIAGNOSTIC T PES AND ACTION:
MMR = MACHINE SHUTDOWN - MANUAL RESET
MAR = MACHINE SHUTDOWN - AUTO RESET
IFW
= INFORMATION - WARNING May or may not affect machine
operation; lowest level of diagnostic.
Remotely Resettable Diagnostics:
Except for the following, all diagnostics can be reset remotely from
either the Remote Clear Language Display or the Tracer. The
following diagnostics shall only be resettable ONLY at the local Clear
Language Display, e.g., with the operator standing at the unit.
Diagnostic Description
Code
Diag
Type
Can Be
Remotely Reset
Starter Contactor Interrupt Failure
CA
MMR No
Phase Loss
E4
MMR No
Phase Reversal
E5
MMR No
High Bearing #1 Temp
EA
MMR No
High Bearing #2 Temp
Eb
MMR No
Current Overload
ECMMR No
Starter did not Transition
F0
MMR No
High Pressure Cutout Tripped
F5
MMR No
Loe Evap Rfgt Temp
Fb
MMR No
Emergency Stop Input
Fd
MMR No
Starter Dry Run Test
188
MMR No
Solid State Starter Fault Rly Clsd
189
MMR No
Diagnostic Description
Code
Diag
Type
Can Be
Remotely Reset
High Motor Temp Position #1
18b
MMR No
High Motor Temp Position #2
18CMMR No
High Motor Temp Position #3
18d
MMR No
Severe Phase Unbalance
1b2
MMR No
Starter Fault Type I
1E9
MMR No
Starter Fault Type II
1Ed
MMR No
Cprs did not Accelerate: Shutdown
EE
MMR No
Adapt Freq Drive Fault Relay Open
18A
MMR No
Transition Complete Input Shorted
3D5
MMR No
At Speed Input Shorted
3D6
MMR No
At Speed Input Opened
3D8
MMR No
Run Fault
4c2
MMR No