Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Maintenance Procedures
Cleaning the Condenser
CAUTION: Proper Water Treatment!
The use of untreated or improperly treated water may
result in scaling, erosion, corrosion, algae or slime. It
is recommended that the services of a qualified water
treatment specialist be engaged to determine what
water treatment, if any, is required. The manufacturer
assumes no responsibility for equipment failures which
result from untreated or improperly treated water, saline
or brackish water.
Compressor Oil
CAUTION: Equipment Damage!
To prevent oil sump heater burnout, open the unit main
power disconnect switch before removing oil from
the compressor.
Trane Polyolester Oil is the approved oil for the unit.
Polyolester oil is extremely hygroscopic meaning it
readily attracts moisture. The oil can not be stored in
plastic containers due to the hygroscopic properties.
As with mineral oil, if water is in the system it will react
with the oil to form acids. Use Table 6 to determine
the acceptability of the oil. Trane approved oil is
OIL0066E/OIL0067E. The proper charge amounts are
given on General data. Note: Use an oil transfer pump
to change the oil regardless of chiller pressure.
For R1234ze, approved oil is OIL0066E/OIL0067E.