RLC-SVX023A
38
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Periodic Maintenance
Overview
This section describes preventative maintenance
procedures and intervals. Use a periodic maintenance
program to ensure optimal performance and efficiency
of the units. An important aspect of the chiller
maintenance program is the regular completion of the
“Operating Log “. When filled out properly the completed
logs can be reviewed to identify any developing trends in
the chiller’s operating conditions.
Weekly Maintenance and Checks
After the unit has operated for approximately 30 minutes
and the system has stabilized, check the operating
conditions and complete the procedures below:
• Log the chiller.
• Check evaporator and condenser pressures with gauges
and compare to the reading on the Clear Language
Display. Pressure readings should fall within the
following ranges specified in the Operating Conditions.
NOTE:
Optimum condenser pressure is dependent on
condenser water temperature, and should equal the
saturation pressure of the refrigerant at a temperature 1
to 3°C above that of leaving condenser water at full load.
Monthly Maintenance and Checks
• Review operating log.
• Clean all water strainers in both the chilled and
condensing water piping systems.
• Measure the oil filter pressure drop. Replace oil filter if
required. Refer to “Service Procedures “.
• Measure and log the subcooling and superheat.
• If operating conditions indicate a refrigerant shortage,
leak check the unit using soap bubbles.
• Repair all leaks.
• Trim refrigerant charge until the unit operates in the
conditions listed in the note below.
Table 4 – Operating Conditions at Full Load R1234ze
Description
Condition
Evaporator pressure
3.5 bar
Condensing pressure
9.4 bar
Discharge superheat
3K
Subcooling
5K
All conditions stated above are based on the unit running
fully loaded, running at conditions indicated above. If full
load conditions can not be met, refer to note below to
trim the refrigerant charge
Note:
entering condenser water: 30°C and entering
evaporator water: 12°C.