RLC-SVX023A
17
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
RTSF Low Refrigerant temperature Ethylene Glycol and Propylene Glycol and Freeze protection settings.
Table 3 – Recommended low evaporator refrigerant temperature cutout (LERTC) and low water temperature cutout
(LWTC) for RTSF chillers
Ethylene Glycol
Mono Propylene Glycol
Glycol
Percentage
(weight %)
Solution
Freeze
Point (°C)
Minimum
Recommended
LRTC
(°C)
Minimum
Recommended
LWTC
(°C)
Solution
Freeze
Point (°C)
Minimum
Recommended
LRTC
(°C)
Minimum
Recommended
LWTC
(°C)
0
0.0
0.0
2.8
0.0
0.0
2.8
2
-0.6
-1.4
2.2
-0.6
-1.4
2.2
4
-1.3
-2.1
1.5
-1.2
-2.0
1.6
5
-1.7
-2.5
1.1
-1.5
-2.3
1.3
6
-2.0
-2.9
0.7
-1.8
-2.6
1.0
8
-2.8
-3.6
0.0
-2.5
-3.3
0.3
10
-3.6
-4.5
-0.8
-3.1
-4.0
-0.4
12
-4.5
-5.3
-1.7
-3.8
-4.7
-1.1
14
-5.4
-6.2
-2.6
-4.6
-5.4
-1.8
15
-5.9
-6.7
-3.1
-5.0
-5.8
-2.2
16
-6.3
-7.2
-3.6
-5.4
-6.2
-2.6
18
-7.4
-8.2
-4.6
-6.2
-7.0
-3.4
20
-8.4
-9.3
-5.7
-7.1
-7.9
-4.3
22
-9.6
-10.4
-6.8
-8.0
-8.8
-5.2
24
-10.8
-11.6
-8.0
-9.0
-9.9
-6.3
25
-11.4
-12.3
-8.7
-9.6
-10.4
-6.8
26
-12.1
-12.9
-9.3
-10.1
-11.0
-7.4
28
-13.5
-14.3
-10.7
-11.3
-12.2
-8.5
30
-15.0
-15.8
-12.2
-12.6
-13.4
-9.8
32
-16.5
-17.3
-13.7
-14.0
-14.8
-11.2
34
-18.2
-19.0
-15.0
-15.5
-16.3
-12.7
35
-19.0
-19.9
-15.0
-16.3
-17.1
-13.5
36
-19.9
-20.6
-15.0
-17.1
-17.9
-14.3
38
-21.8
-20.6
-15.0
-18.8
-19.6
-15.0
40
-23.8
-20.6
-15.0
-20.7
-20.6
-15.0
42
-25.9
-20.6
-15.0
-22.6
-20.6
-15.0
44
-28.1
-20.6
-15.0
-24.8
-20.6
-15.0
45
-29.3
-20.6
-15.0
-25.9
-20.6
-15.0
46
-30.5
-20.6
-15.0
-27.1
-20.6
-15.0
48
-33.0
-20.6
-15.0
-29.5
-20.6
-15.0
50
-35.6
-20.6
-15.0
-32.1
-20.6
-15.0
CAUTION!
1. Additional glycol beyond the recommendations will adversely
affect unit performance. The unit efficiency will be reduced and the
saturated evaporator temperature will be reduced. For some operating
conditions this effect can be significant.
2. If additional glycol is used, then use the actual % glycol to establish the
low refrigerant cutout set point.
3. The minimum low refrigerant cutout set point allowed is - 20.6°C.
This minimum is established by the solubility limits of the oil in the
refrigerant.
4. With glycol application, ensure that there is no fluctuation of brine
flow versus Order Write Up value, as a reduction of flow will adversely
affect unit performance and behaviour.
5. Tables above should not be interpreted as suggesting operating ability
or performance characteristics at all tabulated glycol percentages.
Full unit simulation is required for proper prediction of unit
performance for specific operating conditions. For information on
specific conditions, contact Trane.
Installation - Mechanical