Technical Data

FWD

08

12

20

30

45

Power supply

(V/Ph/Hz)

230/1/50

Capacities
Cooling capacity on water (1)

(kW)

5,2

8,3

15

18,8

30,1

Heating capacity on water (2)

(kW)

6,3

11,9

18,9

20,9

38,2

Fan motor

(type)

2 x direct drive centrifugal

Fan power input (3)

(kW)

0,23

0,46

0,65

1,04

1,51

Current amps (3)

(A)

1,1

2,2

3,1

4,7

5,5

Start-up amps

(A)

3,2

5,5

9,3

14,1

16,5

Air flow
minimum

(m

3

/h)

490

980

1400

1800

2700

nominal

(m

3

/h)

820

1650

2300

3000

4500

maximum

(m

3

/h)

980

1970

2600

3600

5400

Main coil
Water entering/leaving connections

(type)

ISO R7 rotating female

(Dia)

3/4"

3/4"

1 1/2"

1 1/2"

1 1/2"

Electric heater (accessory for blower only)
Electric power supply

(V/Ph/Hz)

230/1/50

230/1/50 or 400/3/50

400/3/50

400/3/50

400/3/50

Heating capacity

(kW)

2/4

8

10

12

12

Hot water coil (accessory for blower only)
Heating capacity (4)

(kW)

6,3

12

17,4

22,4

34,5

G2 filter (filter box accessory)
Quantity

2

2

2

2

2

Dimensions ( LxWxth)

(mm)

386x221x8

486x271x8

586x321x8

586*421*8

586*621*8

G4 filter (filter box accessory)
Quantity

-

2

2

2

2

Dimensions ( LxWxth)

(mm)

-

486x264x48

586x314x48

586*414*48

586*614*48

Condensate pump (accessory)

(type)

Centrifugal

Water flow - lift height

(l/h - mm)

24 - 500

Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)

(dB(A))

36/40/43

38/41/44

46/50/53

47/52/57

47/52/58

Sound power level (5)

(dB(A))

46/50/53

48/51/54

56/60/63

57/62/67

57/62/68

Unit dimensions
Width x Depth

(mm)

890 x 600

1090 x 710

1290 x 820

1290 x 970

1290 x 1090

Height

(mm)

250

300

350

450

650

Shipped unit dimensions
Width x Depth

(mm)

933 x 644

1133 x 754

1333 x 864

1333 x 1008

1333*1133

Height

(mm)

260

310

360

460

660

Weight

(kg)

32

46

61

76

118

Colour

galvanised steel

Recommended fuse size
Unit alone (aM/gI)

(A)

8/16

8/16

8/16

8/25

8/25

Unit with electric heater (gI)

(A)

16 (2kW),25 (4kW)

40 (230V),3*16 (400V)

3*20

3*25

3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

Installation - Mechanical

Storage

If the chiller is to be stored more than one month prior to 
installation, observe the following precautions:

•  Do not remove the protective coverings from the 

electrical panel.

•  Store the chiller in a dry, vibration-free, secure area.

•  At least every three months, attach a gauge and 

manually check the pressure in the refrigerant circuit. 
If the refrigerant pressure is below 3.4 bar at 21°C (2 bar 
at 10 °C), call a qualified service organization and the 
appropriate Trane sales office.

NOTE:

 Pressure will be approximately 1.0 bar if shipped 

with the optional nitrogen charge.

Noise Considerations

•  Refer to Engineering Bulletin for sound consideration 

applications.

•  Locate the unit away from sound-sensitive areas.

•  Install the isolation pads under the unit. Refer to “Unit 

Isolation.”

•  Install rubber vibration isolators in all water piping.

•  Use flexible electrical conduit for final connection to the 

Tracer UC800.

•  Seal all wall penetrations.

NOTE:

 Consult an acoustical engineer for critical 

applications.

Foundation

Provide rigid, non-warping mounting pads or a concrete 
foundation of sufficient strength and mass to support the 
chiller operating weight (including completed piping and 
full operating charges of refrigerant, oil and water).

Refer to General information for unit operating weights.

Once in place, level the chiller within 5 mm over its 
length and width.

The manufacturer is not responsible for equipment 
problems resulting from an improperly designed or 
constructed foundation.

Vibration Eliminators

•  Provide rubber boot type isolators for all water piping 

at the unit.

•  Provide flexible conduit for electrical connections to the 

unit.

•  Isolate all pipe hangers and be sure they are not 

supported by main structure beams that could 
introduce vibration into occupied spaces.

•  Make sure that the piping does not put additional stress 

on the unit.

NOTE:

 Do not use metal braided type eliminators on the 

water piping. Metal braided eliminators are not effective 
at the frequencies at which the unit will operate.

Clearances

Provide enough space around the unit to allow the 
installation and maintenance personnel unrestricted 
access to all service points. A minimum of 1 m is 
recommended for compressor service and to provide 
sufficient clearance for the opening of control panel 
doors. In all cases, local codes will take precedence 
over these recommendations. If the room configuration 
requires a variance to the clearance dimensions, contact 
your sales representative.

NOTE:

 Required vertical clearance above the unit is at 

least 1 m. There should be no piping or conduit located 
over the compressor motor.

NOTE:

 Maximum clearances are given. Depending on 

the unit configuration, some units may require less 
clearance than others in the same category. 

Ventilation

The unit produces heat even though the compressor is 
cooled by the refrigerant. Make provisions to remove 
heat generated by unit operation from the equipment 
room. Ventilation must be adequate to maintain an 
ambient temperature lower than 40°C. Vent the pressure 
relief valves in accordance with all local and national 
codes. Refer to “Pressure Relief Valves”. Make provisions 
in the equipment room to keep the chiller from being 
exposed to ambient temperatures below 10°C.

Water Drainage

Locate the unit near a large capacity drain for water 
vessel drain-down during shutdown or repair. Condenser 
and evaporator water pipes are provided with drain 
connections. Refer to “Water Piping.” All local and 
national codes apply.

Access Restrictions

Refer to the unit submittals for specific dimensional 
information (documents supplied in document package 
coming with unit).

Summary of Contents for City RTSF050

Page 1: ...RLC SVX023A Water cooled Liquid Chillers with Helical Rotary Compressors RTSF 180 385kW R1234ze Installation Operation Maintenance...

Page 2: ...54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644...

Page 3: ...oderate injury It may also be used to alert against unsafe practices or for equipment or property damage only accidents Safety Recommendations To avoid death injury equipment or property damage the fo...

Page 4: ...ax 11 bars Introduction Unit Description The RTSF units are helical rotary type water cooled liquid chillers designed for installation indoors The RTSF units are packaged with an evaporator and conden...

Page 5: ...denserTemp H Cooling Mode Above 50 C Leaving CondenserTemp L Heat pump Below 50 C Leaving CondenserTemp M Heat pump Above 50 C Leaving CondenserTemp Digit 17 Refrigerant Z R1234ze unit with Factory ch...

Page 6: ...size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet tempera...

Page 7: ...t power factor 0 95 0 95 0 95 0 95 0 95 0 95 Short Circuit Unit Capacity kA 35 35 35 35 35 35 Max Power cable cross mm 1x 240 1x 240 1x 240 1x 240 1x 240 1x 240 Disconnect switch size 3 A 400 400 400...

Page 8: ...1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour...

Page 9: ...install valves in the water piping upstream and downstream of the evaporator and condenser to isolate the heat exchangers for maintenance and to balance trim the system Supply and install flow switch...

Page 10: ...ganization and the appropriateTrane sales office NOTE Pressure will be approximately 1 0 bar if shipped with the optional nitrogen charge Noise Considerations Refer to Engineering Bulletin for sound c...

Page 11: ...HUETTERUNGEN UNBEDINGT VERMEIDEN SPECIAL LIFTING AND MOVING INSTRUCTIONS IT IS RECOMMENDED TO USE THE SPECIAL BUILT IN RIGGING POINTS SHOWN IN THE DIAGRAM AND TO FOLLOW THE FOLLOWING INSTRUCTIONS 1 CA...

Page 12: ...e blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute se...

Page 13: ...general locations are given below Entering Chilled Water Piping Air vents to bleed air from system Water pressure gauges with shutoff valves Pipe unions Vibration eliminators rubber boots Shutoff iso...

Page 14: ...rature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Installation Mechanical Water Pressure Relief Valves Install a pressure relief valve in both evaporator and condenser water sys...

Page 15: ...50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56...

Page 16: ...with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is...

Page 17: ...Recommended LRTC C Minimum Recommended LWTC C 0 0 0 0 0 2 8 0 0 0 0 2 8 2 0 6 1 4 2 2 0 6 1 4 2 2 4 1 3 2 1 1 5 1 2 2 0 1 6 5 1 7 2 5 1 1 1 5 2 3 1 3 6 2 0 2 9 0 7 1 8 2 6 1 0 8 2 8 3 6 0 0 2 5 3 3 0...

Page 18: ...hanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 b...

Page 19: ...59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52...

Page 20: ...r gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving te...

Page 21: ...tor start run and AFD Adaptive Frequency Drive capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized For variable frequency drives o...

Page 22: ...project engineer Water Pump Power Supply Provide power supply wiring with fused disconnect for both the chilled water and condenser water pumps Electrical Panel Power Supply Power supply wiring instr...

Page 23: ...2 LRA At 240 VAC 5 0 amp resistive 2 0 amp pilot duty 250 W 3 6 FLA 21 3 LRA Installation Electrical Whenever a dry contact input binary input is referenced the electrical rating is 24VDC 12 mA Whene...

Page 24: ...s Installation Electrical Condenser Water Pump Control Tracer UC800 provides a contact closure output to start and stop the condenser water pump It will allow to run the condenser pump after compresso...

Page 25: ...ut TheTracer UC800 provides auxiliary control for a customer specified installed latching trip out When this customer furnished remote contact is provided the chiller will run normally when the contac...

Page 26: ...LCI C between the chiller and a BAS An LCI C LLID shall be used to provide gateway functionality between the LonTalk protocol and the chiller Bacnet Communication Interface Optional Tracer UC800 provi...

Page 27: ...top condition Diagnostic information is provided to allow the operator to identify system malfunctions Note To ensure proper diagnosis and repair contact a qualified service organization if a problem...

Page 28: ...pressure min 1 bar max 11 bars Operating Principles Mechanical Cycle Description The refrigeration cycle for the chiller can be described using the pressure enthalpy diagram shown in Figure 5 Key Stat...

Page 29: ...55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 6...

Page 30: ...min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Operating Principles Mechanical Compressors The compressor used by...

Page 31: ...61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 1...

Page 32: ...op of the oil separator and is discharged into the condenser Oil that collects in the bottom of the oil separator at condensing pressure during compressor operation therefore oil is constantly moving...

Page 33: ...4 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horiz...

Page 34: ...inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water e...

Page 35: ...on is complete before starting the unit the following prestart procedures must be reviewed and verified 1 Inspect all wiring connections in the compressor power circuits disconnects terminal block con...

Page 36: ...ering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the b...

Page 37: ...t up procedures as follows 1 Check the evaporator refrigerant pressure and the condenser refrigerant pressure under Refrigerant Report on theTD7 2 Check the EXV sight glasses after enough time has ela...

Page 38: ...minal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature m...

Page 39: ...r can not be inadvertently energized Failure to disconnect power before servicing could result in death or serious injury Shut down the chiller once each year to check the following Perform all weekly...

Page 40: ...e 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water t...

Page 41: ...63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Maintenance...

Page 42: ...max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Maintenance Procedures Table 6 POE Oil Properties Description Acceptable Leve...

Page 43: ...c Loss of oil at the compressor stopped will be generated if the oil lines are not full on start up To properly charge the system with oil follow the steps below 1 Locate the 1 4 schrader valve on the...

Page 44: ...s Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8...

Page 45: ...refrigerant Once the problem is repaired follow the procedures below for evacuating and charging the unit Refrigerant recovery 1 Insure that the water flow is maintained on condenser and evaporator d...

Page 46: ...let temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool du...

Page 47: ...newal To ensure a long lifetime forTrane compressors system oil and vibration are regularly analyzed These tests build a detailed picture of the condition of internal system components Over time they...

Page 48: ...rtfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane eu Trane has a policy of continuous product and product data improvement an...

Reviews: