WSHP-SVX13C-EN
45
Electrical Data
WARNING
Rotating Components!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Table 40. VSH* electrical data with ECM option
Model No.
Unit Volts
Total Unit
FLA
Comp RLA
(ea)
No. of
Compressors
Blower
Motor FLA
Blower
Motor hp
Fan
Motor
Num.
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
VSH024
208/60/1
10.2
9.2
1
0.97
1/2
1
12.47
20
230/60/1
10.2
9.2
1
0.97
1/2
1
12.47
20
460/60/3
3.7
2.9
1
1.29
1/2
1
4.43
15
VSH033
208/60/1
14.4
12.9
1
1.48
1/2
1
17.61
30
230/60/1
14.4
12.9
1
1.48
1/2
1
17.61
30
460/60/3
5.5
4.2
1
1.29
1/2
1
6.54
15
VSH042
208/60/1
15.1
13.1
1
2.03
1
1
18.41
30
230/60/1
15.1
13.1
1
2.03
1
1
18.41
30
460/60/3
6.1
4.2
1
1.86
1
1
7.11
15
VSH050
208/60/1
20.5
17.8
1
2.69
1
1
24.94
40
230/60/1
20.5
17.8
1
2.69
1
1
24.94
40
460/60/3
7.5
5.0
1
2.48
1
1
8.73
15
VSH060
208/60/1
25.8
21.8
1
4.03
1
1
31.28
50
230/60/1
25.8
21.8
1
4.03
1
1
31.28
50
460/60/3
8.8
4.9
1
3.84
1
1
10.00
15
Table 41. VSV* electrical data with ECM option
Model No.
Unit Volts
Total Unit
FLA
Comp RLA
(ea)
No. of
Compressors
Blower
Motor FLA
Blower
Motor hp
Fan
Motor
Num.
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
VSV024
208/60/1
11.3
9.2
1
2.1
3/4
1
13.6
20
230/60/1
11.3
9.2
1
2.1
3/4
1
13.6
20
460/60/3
4.9
2.9
1
2.0
3/4
1
5.6
15
VSV033
208/60/1
15.7
12.9
1
2.8
3/4
1
18.9
30
230/60/1
15.7
12.9
1
2.8
3/4
1
18.9
30
460/60/3
6.9
4.2
1
2.7
3/4
1
8.0
15
VSV042
208/60/1
17.7
13.1
1
4.6
1
1
20.9
30
230/60/1
17.7
13.1
1
4.6
1
1
20.9
20
460/60/3
8.2
4.2
1
4.0
1
1
9.3
15
VSV050
208/60/1
24.8
17.8
1
7.0
1
1
29.3
45
230/60/1
24.8
17.8
1
7.0
1
1
29.3
45
460/60/3
11.6
5.0
1
6.6
1
1
13.25
15
VSV060
208/60/1
25.8
21.8
1
4.03
1
1
31.28
50
230/60/1
25.8
21.8
1
4.03
1
1
31.28
50
460/60/3
8.8
4.9
1
3.84
1
1
10.00
15