General Data
38
WSHP-SVX13C-EN
Table 33. Water volume
Model VSV*
VSV*024
VSV*033
VSV*042
VSV*050
VSV*060
Internal water volume (in
3
)
212
212
414
414
414
Internal water volume (ft
3
)
0.123
0.123
0.24
0.24
0.24
Internal water volume (gal)
0.918
0.918
1.792
1.792
1.792
Table 34. ISO Ratings (VSH)
(a)
Water Loop Heat Pump
Ground Water Heat Pump
Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F
Full Cool 77°F
Part Cool 68°
Full Heat 32°F
Part Heat 41°F
Model
Load
Rated
GPM
Rated
CFM
Capacity
Btuh
EER
Capacity
Btuh
COP
Capacity
Btuh
EER
Capacity
Btuh
COP
Capacity
Btuh
EER
Capacity
Btuh
COP
VSH*024
Full
6.2
930 25,100
18.30
30,300
6.44
28,400
31.76
24,300
5.33
26,200
21.82
18,500
4.35
Partial
625 13,800
23.67
15,900
8.64
15,500
48.23
12,400
6.37
15,000
36.43
10,300
4.99
VSH*033
Full
8.6
1200 33,800
15.79
40,200
5.85
37,900
25.01
32,300
4.98
35,300
18.51
24,700
4.10
Partial
720 17,600
21.96
21,000
7.71
19,700
41.82
16,600
5.94
18,900
32.23
14,300
4.96
VSH*042
Full
10.5
1650 42,600
18.60
51,800
6.70
47,300
30.90
42,000
5.60
44,600
22.00
31,500
4.50
Partial
1065 24,100
23.26
29,800
8.21
27,200
48.49
23,500
6.45
26,100
35.38
18,800
5.39
VSH*050
Full
12.7
1890 50,200
16.50
64,400
5.80
56,200
26.00
52,500
5.10
52,400
19.30
40,100
4.20
Partial
1200 28,400
22.29
36,100
7.52
32,400
42.02
29,100
6.16
31,000
33.67
24,000
5.28
VSH*060
Full
15.6
2100 60,700
14.80
81,600
5.30
67,300
22.80
66,800
4.70
63,200
17.00
50,400
3.80
Partial
1323 36,400
20.56
46,500
6.77
40,900
37.58
37,400
5.72
39,100
31.43
31,300
5.06
(a) Rated in accordance with ISO Standard 13256-1 - 1 1998, Water-to-Air and Brine-to-Air Heat Pumps. Certified conditions are 80.6°F DB/66.2°F WB
EAT in cooling and 68°F DB/59°F WB EAT in heating. Entering liquid temperature in cooling is 86°F for Water Loop, 77°F for Ground Loop (full load),
68°F for Ground Loop (part load), and 59°F for Ground Water. Entering liquid temperature in heating is 68°F for Water Loop, 32°F for Ground Loop (full
load), 41°F for Ground Loop (part load), and 50°F for Ground Water.
Table 35. ISO Ratings (VSV)
(a)
Water Loop Heat Pump
Ground Water Heat Pump
Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F
Full Cool 77°F
Part Cool 68°
Full Heat 32°F
Part Heat 41°F
Model
Load
Rated
GPM
Rated
CFM
Capacity
Btuh
EER
Capacity
Btuh
COP
Capacity
Btuh
EER
Capacity
Btuh
COP
Capacity
Btuh
EER
Capacity
Btuh
COP
VSV*024
Full
6.2
930 24,600
18.44
30,300
6.10
27,800
33.24
24,400
5.20
25,900
22.32
18,400
4.17
Partial
625 13,100
22.58
15,900
7.62
15,000
48.48
12,100
6.13
14,300
35.31
9,900
4.81
VSV*033
Full
8.3
1200 32,900
15.47
40,400
5.46
36,600
24.67
32,400
4.77
34,300
18.08
24,500
3.86
Partial
720 17,100
20.81
21,500
6.96
19,400
40.79
16,800
5.59
18,500
31.59
14,100
4.60
VSV*042
Full
10.9
1650 44,100
18.25
54,700
5.95
50,100
32.46
43,600
5.08
46,200
22.03
31,900
3.98
Partial
1065 25,500
24.17
29,400
7.50
28,700
51.26
22,700
5.85
26,900
40.50
17,800
4.59
VSV*050
Full
13.0
1890 51,200
15.72
68,800
5.32
57,800
26.19
54,600
4.58
54,100
18.76
41,400
3.75
Partial
1200 29,900
22.08
36,800
6.88
33,500
42.46
28,500
5.50
32,800
34.00
23,400
4.62
VSV*060
Full
15.6
2100 61,800
15.60
81,200
5.50
70,400
25.40
65,400
4.80
64,600
18.30
50,000
4.00
Partial
1323 35,900
21.28
46,300
7.30
41,300
41.38
36,200
5.91
39,600
32.88
30,400
5.29
(a) Rated in accordance with ISO Standard 13256-1 - 1 1998, Water-to-Air and Brine-to-Air Heat Pumps. Certified conditions are 80.6°F DB/66.2°F WB
EAT in cooling and 68°F DB/59°F WB EAT in heating. Entering liquid temperature in cooling is 86°F for Water Loop, 77°F for Ground Loop (full load),
68°F for Ground Loop (part load), and 59°F for Ground Water. Entering liquid temperature in heating is 68°F for Water Loop, 32°F for Ground Loop (full
load), 41°F for Ground Loop (part load), and 50°F for Ground Water.