Figure 19. Units with UC400 controls and ECM motors –
DIP switch settings
Installation
WSHP-SVX10H-EN
21
Installations at altitudes above 2000 feet may require an
adjustment to the fan speed setting to achieve the proper
airflow. To adjust the airflow to get the desired CFM, set the DIP
switches located in the control box to the proper profile setting.
Tracer
®
TU can be used to make further adjustments to the fan
speed.
Use the following table to select the correct profile to use.
Table 12. Profiles for altitude range
Profile
Altitude (Feet)
A
0–2000
B
2000–4000
C
4000–6000
D
Above 6000
Table 13. PSC blower motor external static pressure without return air door (RAD) with filter
Model
External Static Pressure (in. of wg)
Speed
Tap
Ducted
(a)
Unit
CFM
0
0.05
0.10
0.15
0.20
0.25
Max
Min
CFM
KW
CFM
KW
CFM
KW
CFM
KW
CFM
KW
CFM
KW
GET009
High
Yes
408
421
0.108
388
0.107
354
0.106
320
0.104
283
0.103
244
0.102
Low
Yes
355
0.073
332
0.072
307
0.070
278
0.068
245
0.067
High
No
357
0.073
333
0.071
309
0.070
282
0.069
253
0.067
Low
No
272
307
0.061
297
0.060
280
0.059
258
0.058
GET012
High
Yes
453
453
0.140
433
0.137
412
0.134
390
0.130
367
0.127
342
0.124
Low
Yes
401
0.112
383
0.109
362
0.106
340
0.103
318
0.100
295
0.097
High
No
418
0.125
400
0.122
379
0.120
356
0.117
332
0.113
309
0.110
Low
No
304
345
0.097
331
0.095
313
0.092
292
0.090
GET015
High
Yes
648
652
0.191
634
0.187
616
0.183
598
0.179
Low
Yes
560
0.155
539
0.153
523
0.152
511
0.149
499
0.146
487
0.143
High
No
553
0.169
538
0.167
524
0.165
510
0.162
496
0.159
481
0.155
Low
No
432
445
0.135
433
0.135
422
0.134
GET018
High
Yes
780
Low
Yes
665
0.253
644
0.249
625
0.246
608
0.242
592
0.237
575
0.232
High
No
696
0.361
675
0.354
654
0.348
632
0.342
610
0.336
588
0.330
Low
No
520
544
0.271
526
0.266
506
0.262
GET024
High
Yes
984
988
0.402
Low
Yes
908
0.344
895
0.335
876
0.327
854
0.318
829
0.310
803
0.301
High
No
850
0.317
827
0.310
806
0.303
787
0.297
768
0.291
750
0.286
Low
No
656
799
0.292
781
0.286
764
0.280
746
0.275
727
0.269
709
0.264
GET036
High
Yes
1404
Low
Yes
1303
0.651
1293
0.638
1282
0.625
1270
0.614
1256
0.603
1240
0.592
High
No
1330
0.642
1304
0.630
1277
0.618
1248
0.606
1219
0.593
1188
0.581
Low
No
936
1059
0.523
1051
0.516
1042
0.510
1033
0.503
1022
0.496
1011
0.488
Model
External Static Pressure (in. of wg)
Speed
Tap
Ducted
Unit
CFM
0.30
0.35
0.40
0.45
0.50
0.55
Max
Min
CFM
KW
CFM
KW
CFM
KW
CFM
KW
CFM
KW
CFM
KW
GET012
High
Yes
453
316
0.121
288
0.118
Low
Yes
High
No
286
0.107
Low
No
304