background image

Installation

20

 WSHP-SVX10H-EN

PSC Blower Motor Speed Retrofit

PSC motors installed in the unit have multiple speed 
configurations. To modify the rpm of the motor, the following 
steps may be followed.

WARNING

Hazardous Voltage!

Failure to disconnect power before servicing could 

result in death or serious injury. 

Disconnect all electric power, including remote 

disconnects before servicing. Follow proper lockout/

tagout procedures to ensure the power can not be 

inadvertently energized. Verify that no power is present 

with a voltmeter.

1. Locate the blower motor relay inside the chassis control 

box.

2. Remove the undesired speed tap.
3. Select desired speed tap wire by using information from 

Table 11, p. 20

.

4. Connect desired tap wire to the 1K4 relay at spade 4.
5. Reconnect power to the unit.

Table 11. Lead change

Lead Colors

Lead Speed

High

Low

Blower

1G

9A

ECM CFM Settings

To adjust the CFM, disconnect the power to the unit. Set the 
DIP switch located in the control box to the desired profile 
setting. Connect the power to the unit.

Figure 18. Units with Deluxe 24V or Tracer 

®

 ZN510 

controls and ECM motors – DIP switch 
settings

Note:

Units with the optional ECM with deluxe 24V or 
Tracer® ZN510 controls are shipped from the factory 
on Profile B.

Profile A = 110% of rated airflow

Profile B = 100% of rated airflow

Profile C = 90% of rated airflow

Profile D = 80% of rated airflow

Installation at higher altitudes may require an adjustment to the 
fan speed setting to achieve proper airflow. Use profile C or D 
to get lower airflow. If a lower CFM is needed, then set DIP 
switch 4 to ON.

ON

FLASH

OFF

Manual Lockout (condensate 

overflow)

ON

ON

OFF

Compressor Disable

Table 10. Deluxe controller diagnostic LEDs (continued)

Color: Green

Color: Red

Controller Mode

LED1

LED2

LED3

Summary of Contents for Axiom GET024-036

Page 1: ...uipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or...

Page 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the app...

Page 3: ...y of Trane and may not be used or reproduced in whole or in part without written permission Trane reserves the right to revise this publication at any time and to make changes to its content without o...

Page 4: ...g Hinged Acoustic Door Assembly 16 Supply Air Ductwork 17 Chassis Installation 17 Supply Grille Installation 18 Cleaning and Flushing the Water Loop 18 Using Antifreeze 19 Low Voltage Wiring 19 Low Vo...

Page 5: ...turn air door tamper resistant HEX 4 Hinged return air door with key lock Digit 17 Control Types C Tracer ZN510 controls D Deluxe 24V controls H UC400 B J UC400 B with Air Fi Wireless Communications D...

Page 6: ...0 Open Digit 15 Supply Air Arrangement 0 Field cut supply air arrangement 1 Back and front supply air arrangement 2 Back and left supply air arrangement 3 Back and right supply air arrangement 4 Front...

Page 7: ...tion around the compressor enclosure and vibration isolation between the chassis and cabinet An additional dampening treatment is applied around the compressor enclosure to achieve greater acoustical...

Page 8: ...claims MAY NOT be accepted by the freight company Verify that the refrigerant charge has been retained during shipment by use of gauges Schrader taps are located external to the cabinet on the 3 ton e...

Page 9: ...175 150 024 225 195 036 225 195 Chassis 009 88 78 012 107 97 015 112 102 018 117 107 024 174 164 036 190 180 Unit Location and Clearances Locate the unit in an indoor area The ambient temperature surr...

Page 10: ...s and Weights with Standard Base Figure 2 GET009 036 Table 2 Dimensional data GET009 036 w standard base GET A inches B inches C inches D inches E inches F inches 009 012 16 16 8 1 8 39 1 8 14 015 018...

Page 11: ...ET009 036 11 279 FOR 86 2184 CABINET HEIGHT 3 76 FOR 94 2388 CABINET HEIGHT 66 10 3 4 8 1 2 Table 3 Dimensional data GET009 036 with 6 inch extended base GET A inches B inches C inches D inches E inch...

Page 12: ...1 8 54 5 8 Figure 4 Return air hinged acoustical door with standard base RETURN AIR OPENING FLANGE ON CABINET RETURN AIR OPENING FLANGE ON CABINET 2 X 4 STUD A B SHEET ROCK OPENING TOP VIEW SIDE VIEW...

Page 13: ...024 036 27 1 8 54 5 8 Figure 5 Return air hinged acoustical door with 6 inches extended base RETURN AIR OPENING FLANGE ON CABINET RETURN AIR OPENING FLANGE ON CABINET 2 X 4 STUD A B SHEET ROCK OPENING...

Page 14: ...t no power is present with a voltmeter WARNING Proper Field Wiring and Grounding Required Failure to follow code could result in death or serious injury All field wiring MUST be performed by qualified...

Page 15: ...through the cabinet for piping with suitable material to help eliminate air leakage 11 See Cleaning and Flushing the Water Loop p 18 for system flushing Note Remove shipping straps from risers Water C...

Page 16: ...of drywall to allow for frame mounting Units Utilizing Hinged Acoustic Door Assembly Figure 8 Mock up of stud placement 1 Locate the side studs a minimum of 1 inches and a maximum of 1 3 8 inches from...

Page 17: ...r verifying that the air panel gasket is sealed to the coil secure the air panel to the door frame using the slots located on the sides of the air panel Figure 12 Secure to door frame 8 Install filter...

Page 18: ...cabinet discharge opening Ensure there are no air gaps between the cabinet supply air and the grille This helps prevent recirculation of supply air into the return air opening behind the drywall 2 Se...

Page 19: ...ing the cabinet assembly simply plug the male portion of thermostat zone sensor plug into the female portion of the plug located inside the unit s junction box 2 Mount the thermostat zone sensor or Tr...

Page 20: ...to the unit Table 11 Lead change Lead Colors Lead Speed High Low Blower 1G 9A ECM CFM Settings To adjust the CFM disconnect the power to the unit Set the DIP switch located in the control box to the...

Page 21: ...42 0 124 Low Yes 401 0 112 383 0 109 362 0 106 340 0 103 318 0 100 295 0 097 High No 418 0 125 400 0 122 379 0 120 356 0 117 332 0 113 309 0 110 Low No 304 345 0 097 331 0 095 313 0 092 292 0 090 GET0...

Page 22: ...0 472 967 0 464 949 0 454 927 0 444 Model External Static Pressure in of wg Speed Tap Ducted Unit CFM 0 60 0 65 0 70 0 75 0 80 0 85 Max Min CFM KW CFM KW CFM KW CFM KW CFM KW CFM KW GET015 High Yes 64...

Page 23: ...0 0 163 0 177 0 191 0 205 0 087 0 268 0 282 0 282 C 584 0 056 0 066 0 076 0 087 0 099 0 111 0 123 0 135 0 148 0 160 0 172 0 066 0 230 0 242 0 242 D 522 0 039 0 048 0 058 0 069 0 080 0 091 0 102 0 114...

Page 24: ...208 60 1 8 5 7 9 36 0 0 60 1 2 10 48 15 230 60 1 8 5 7 9 36 0 0 60 1 2 10 48 15 265 60 1 7 0 6 4 30 0 0 60 1 2 8 60 15 GET018 FreeDischarge PSC Motor 208 60 1 10 3 9 6 42 0 0 70 1 8 12 70 20 230 60 1...

Page 25: ...between the front air panel and the coil Initial Unit Start up Start up with deluxe controls is included below Notes Reference WSHP IOP 2 for Tracer ZN510 start up Reference BAS SVX065 EN for Tracer...

Page 26: ...3 399 11 14 11 14 199 229 389 496 11 14 21 26 GET 009 86 2 25 146 168 306 389 8 11 11 15 206 237 394 501 9 12 21 27 GET 009 95 1 80 148 170 355 452 11 13 11 14 GET 009 95 2 25 147 170 347 441 8 11 11...

Page 27: ...24 55 6 10 137 158 197 251 9 11 18 23 121 139 302 384 6 7 25 31 GET 024 68 4 70 139 160 246 313 11 14 17 22 142 164 318 405 8 11 27 35 GET 024 68 6 10 139 160 238 303 9 11 18 23 147 169 321 409 7 8 28...

Page 28: ...0 16 7 The following table is provided for use in calculating glycol requirements for the unit Table 20 Water volume Unit Water Side Volume Cubic In Water Side Volume Cubic Ft Water Side Volume Gallon...

Page 29: ...ilures complete the following checks and data entries before the system is put into full operation MODE Heat Cool Entering fluid temperature F F Leaving fluid temperature F F Temperature differential...

Page 30: ...ell water it is important to check the cleanliness of the water to refrigerant heat exchanger Should it become contaminated with dirt and scaling as a result of bad water the heat exchanger will have...

Page 31: ...such as leaking connection broken or disconnected wires etc If everything appears to be in order but the unit still fails to operate properly refer to the troubleshooting chart on p 32 General Operat...

Page 32: ...icted thermal expansion valve Replace X X Defective reversing valve See WSHP IOM for touch test chart X X Thermostat improperly located Relocate X X Unit undersized Recalculate heat gains losses X X I...

Page 33: ...OTROS TIPOS DE CONDUCTORES UTILICE NICAMENTE CONDUCTORES DE COBRE LAS TERMINALES DE LA UNIDAD NO EST N DISE ADAS SI NO LO HACE PUEDE OCASIONAR DA O AL EQUIPO 2309 7379 RCAP6047 4 29 15 5 11 09 LOWE G...

Page 34: ...ES INTO MANUAL LOCKOUT MODE ISOLATED GENERAL ALARM CONTACTS CONTACTS CLOSE 11 52 22B 21A 26H 6 CONTACTS RATED FOR CLASS 2 24V TERMINAL AL1 AL2 L2 L1 M FIELD INSTALLED DEVICE 6 2B1S1 47A 46A 49A 48A B...

Page 35: ...ADAS SI NO LO HACE PUEDE OCASIONAR DA O AL EQUIPO REV SHALL NOT BE COPIED OR ITS THIS DRAWING IS PROPRIETARY AND CONSENT OF THE TRANE COMPANY PARTIES WITHOUT THE WRITTEN CONTENTS DISCLOSED TO OUTSIDE...

Page 36: ...IELD INSTALLED DEVICE 6 2B1S1 47A 46A 49A 48A B 1TB1 1 2 21 7 6 7 37 1TB1 CUSTOMER LOW V TERM BLOCK 6 7 8 53 54 55 56 57 58 59 60 2L1 J9 6 P9 6 J9 5 P9 5 44B 45B P9 1 J9 1 P9 2 J9 2 46B 47B P9 3 J9 3...

Page 37: ...Figure 24 Tracer UC400 B with ECM Unit Wiring WSHP SVX10H EN 37...

Page 38: ...Figure 25 Tracer UC400 B with PSC motor Unit Wiring 38 WSHP SVX10H EN...

Page 39: ...shipment There is a standard five year compressor parts warranty Extended Warranty The optional extended warranty is a second through fifth year warranty The time starts at the end of standard 1 year...

Page 40: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Reviews: