Dimensions and Weights
12
WSHP-SVX10H-EN
Return Air (Hinged) Acoustical Door with Standard Base
The hinged acoustical door is recessed into the wall so that the
door is flush with the surface of the wall.
The opening through the wall for the door assembly must be
centered with the return-air opening of the unit cabinet. For full
installing instructions of the return-air acoustical door, see
Table 4.
Return air hinged acoustical door
Unit Size
A (inches)
B (inches)
009-012
19¼
44 1/8
015-018
23¼
45¼
024-036
27 1/8
54 5/8
Figure 4.
Return air (hinged) acoustical door with standard base
RETURN-AIR OPENING
FLANGE ON CABINET
RETURN-AIR OPENING
FLANGE ON CABINET
2 X 4 STUD
A
B
SHEET ROCK
OPENING
TOP VIEW
SIDE VIEW
CABINET
B
2 1/4“
3 1/2” ±3/8”
3 1/2” ±3/8”
FLOOR
SHEETROCK
SHEETROCK
RETURN AIR
DOOR FRAME
RETURN AIR
DOOR FRAME
1“ X 1” CLOSED
CELL INSULATION
1“ X 1” CLOSED
CELL INSULATION
ROCK
3 1/2” ±3/8”
1 1/4”
+1/2”/-0”
1 1/4”
+1/2”/-0”
A
1“ X 1” CLOSED
CELL INSULATION
1“ X 1” CLOSED
CELL INSULATION
2“ X 4”
STUD
2“ X 4” STUD
RETURN AIR OPENING
FLANGE ON CABINET
RETURN AIR OPENING
FLANGE ON CABINET
SHEETROCK
SHEETROCK
RETURN AIR DOOR FLANGE
CABINET
CABINET
Note:
Finished wall and framing should not
touch the unit cabinetry.
5“
4 5/8“
1 1/2” X 2 3/8”