Dimensions and Weights
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could
result in unit dropping and possibly crushing operator/
technician which could result in death or serious injury,
and equipment or property-only damage.
Test lift unit approximately 24 inches (61 cm) to verify
proper center of gravity lift point. To avoid dropping of
unit, reposition lifting point if unit is not level.
Table 1.
Unit weights
Size
Shipping weight with
pallet (lb)
Shipping weight without
pallet (lb)
Cabinet
009
135
115
012
135
115
015
175
150
018
175
150
024
225
195
036
225
195
Chassis
009
88
78
012
107
97
015
112
102
018
117
107
024
174
164
036
190
180
Unit Location and Clearances
Locate the unit in an indoor area. The ambient temperature
surrounding the unit must not be less than 45°F. Do not locate
the unit in areas subject to freezing.
Attention should be given to service clearance and technician
safety. The unit chassis should be easily removed from the
cabinet in all applications. There must be enough space for
service personnel to perform maintenance or repair. Provide
sufficient room to make water, and electrical connection(s).
Local and national codes should be followed in providing
electrical power connections.
Figure 1.
Mechanical clearances
(a)
(a) Clearance shown is at unit front for chassis removal.
R
S
D
36"