TK 56702-1-OP-EN
Check Alarms
Check Alarms are indicated by an Alarm Icon in the display. The amber K
symbol of the remote indicator alarm light (if installed) will be on. This level
of alarm serves as a notice to take corrective action before a problem
becomes severe. The unit will run with check alarms but some features and
functions may be inhibited.
Shutdown Alarms
Shutdown Alarms will be set if continued operation could cause damage to
the unit or the load. Shutdown Alarms are indicated by the following:
•
The Alarm Icon will appear in the display.
•
The display and backlight will flash on and off.
•
The display will switch from normal to inverted and back to normal (light
areas become dark and dark areas become light).
•
The remote indicator alarm light (if installed) will display only a row of
LEDs at the bottom.
Figure 61.
Shutdown Alarm
Shutdown Alarms will force the unit into shutdown to prevent potential
damage to the unit or load. The unit will remain in shutdown until the
Shutdown Alarm is manually cleared. Exceptions are some engine and
electric Shutdown Alarms that become Log Alarms when switched to the
alternate operating mode (diesel to electric or electric to diesel).
Prevent Alarms
Prevent Alarms are also indicated by a steady Alarm Icon in the display. The
remote indicator alarm light (if installed) will be on. The unit will attempt to
resolve the situation as shown below:
•
The unit will be temporarily shut down if a Prevent Alarm is active.