TK 56702-1-OP-EN
43
Figure 42.
Defrost Display
Terminating a Defrost Cycle
The defrost cycle terminates automatically when the coil temperature is
greater than or equal to 52°F (11°C) or the defrost timer expires. Defrost can
also be terminated by turning the unit off and back on.
Selecting High Speed Lockout Mode (If Enabled)
High speed operation can be locked out in noise sensitive areas if required.
N
No
otte
e:: High Speed Lockout Enable must be set to [Enabled] in the Guarded
Access/Programmable Features Menu or this feature will not be
available.
IIm
mp
po
orrtta
an
ntt:: HIGH SPEED LOCKOUT TIMEOUT: If High Speed Lockout Mode
is selected, the High Speed Inhibit Timeout feature may be set to
return the unit to normal operation after a set time period has
expired. This prevents extended operation with high speed
operation locked out. The time period may be from 15 minutes to
2 hours. If the time period is set and is exceeded, the unit will
return to normal operation, with high speed operation allowed. If
this occurs, the message HIGH SPEED LOCKOUT ACTIVE at the
top of the display will disappear. If necessary to return to High
Speed Lockout Mode, press the High Speed Lockout Key again.
The High Speed Lockout Key is a toggle. If high speed is currently allowed,
pressing the High Speed Lockout Key will disable high speed operation.
Pressing the High Speed Lockout Key again will allow high speed operation.
To change the setting, press the High Speed Lockout key as shown (
).