All files are text-based and can thus be read with any text editor. The separator used in
the files is the tab, so the files are easier to read in Excel, for example.
Event log (EVENTLOG.TXT)
The event log stores all relevant events as plain text with a time stamp.
Power OFF (*)
The device operating voltage
was lost.
Power ON
The device was restarted.
SD Card removed
The memory card was
removed.
SD Card inserted
The memory card was
reinserted.
Insulation Alarm ON [
N
kOhm][
L
kOhm]
The insulation resistance alarm
activated with value
N
,
whereas the limit value has
been
L.
Insulation Alarm OFF
The insulation alarm is no
longer active.
Insulation Alarm Acknowledge
The insulation alarm that is no
longer active was
acknowledged manually.
Alarm Limit changed [Insulation] [
L1
kOhm]-
>[
L2
kOhm]
The insulation resistance alarm
limit value was changed from
L1
to
L2.
Insulation Prealarm ON [
N
kOhm][
L
kOhm]
The insulation pre-alarm
activated with value
N
,
whereas the limit value has
been
L.
Insulation Prealarm OFF
The insulation pre-alarm is no
longer active.
Insulation Prealarm Acknowledge
The insulation pre-alarm that is
no longer active was
acknowledged manually.
Alarm Limit changed [PreInsulation] [
L1
%]->[
L2
%]
The insulation resistance pre-
alarm limit value was changed
from
L1
to
L2.
OverTemperature ON [
N
C][
L
C]
The transformer temperature
alarm activated with value
N
,
whereas the limit value has
been
L.
OverTemperature OFF
The transformer temperature
alarm is no longer active.
OverTemperature Acknowledge
The transformer temperature
alarm was acknowledged
manually.
Alarm Limit changed [Temperature] [
L1
C]->[
L2
C]
The transformer temperature
limit value was changed from
L1
to
L2.
Temperature Sensor Type Changed to NTC
Temperature Sensor Type Changed to Pt100
The type of the transformer’s
temperature sensor was
changed.
Temperature Sensor Calibrated [
O1
ADP]->[
O2
ADP]
The transformer’s temperature
sensor of type Pt100 was
calibrated. The old offset value
Summary of Contents for SUPERINTEND IC-01
Page 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Page 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Page 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Page 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Page 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Page 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...