The following parameters can be changed in the Setup menu:
INSULATION LIMIT
: Alarm limit of the insulation resistance. If the measured
value is lower than the alarm limit, an alarm is given. The setup range is 50
kΩ…1,000 kΩ. It can be set at 50 kΩ intervals.
PRE INSULATION LIMIT:
The pre-insulation limit of the insulation resistance.
Given as a percentage of the insulation limit. Activates the AUX. ALARM relay,
unless it is removed from the AUX alarm mask. The setup range is 100…200%, at
10% intervals.
TEMPERATURE LIMIT:
The alarm limit of the transformer temperature. Can be
set between 30…140 °C or switched OFF if temperature measurement is not
used.
TEMPERATURE SENSOR TYPE:
The type of the temperature sensor used (NTC
or PT100).
PT100 CALIBRATION:
This setting is only used when PT100 is selected as the
temperature sensor. It can compensate for the error caused by long
measurement wires (the maximum loop resistance is 20 Ω) in the temperature
value. A 130 Ω resistor is connected to the end of the measurement wires in the
place of the PT100 sensor, after which calibration is performed:
If the resistance measured in calibration is too low or too high, the message
displayed is Failed, instead of Cal.OK. In that situation, check the connection.
LOAD LIMIT:
The current limit of the transformer as a percentage of the
transformer's nominal current. Can be set between 50…140% or switched OFF if
load current measurement is not used.
TRAN SIZE:
The nominal value of the current transformer. The primary current
that provides a current transformer output current of 5A. The setup range is 10–
100 A.
NOMINAL CURRENT:
The nominal current of the isolation transformer at full
power. SETUP RANGE 1–100 A.
Summary of Contents for SUPERINTEND IC-01
Page 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Page 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Page 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Page 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Page 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Page 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...