6.3.13 Short diagnostics (16 byte)
With this parameter in the TR operation modes the number of diagnostic bytes can be
limited from 6+51 bytes to 6+10 bytes. Therefore the measuring system can be
operated also to Profibus masters with older issue numbers in these modes.
Selection
Default
No
X
Yes
6.3.14 Limit switch lower and upper limit
Is the status switched on (see commissioning function) the measuring system can
inform the master via a bit whether the actual value is within the limits.
It is valid:
Limit switch bit = 0
if lower limit < actual value < upper limit
Limit switch bit = 1
if actual value < lower limit or actual value > upper limit
Input lower limit, depend on the total measuring length in increments
Lower limit
0
Upper limit
Programmed total measuring length in increments - 1
Default
0
Input upper limit, depend on the total measuring length in increments
Lower limit
0
Upper limit
Programmed total measuring length in increments - 1
Default
16 777 215
6.3.15 Rpm. multiplier [1/n rpm]
With this parameter the information of the rotation speed can be scaled in arbitrary
increments between 1/1 and 1/100 rpm.
Input
Lower limit
1
Upper limit
100
Default
1