background image

Fig. #41

M

K

I

A

V

G

G

H

A

J

V

G

A

B

C

A

V

V

A

V

B

F

B

L

V

E

V

V

V

D

A=  clearances above grade, veranda, porch, deck, or balcony  

[* 12 inches (30 cm) minimum]

B=  clearance to window or door that may be opened [* 12 

inches (30 cm) minimum]

C=  clearance to permanently closed window [minimum 12 

inches (30 cm) recommended to prevent condensation on 
window]

D=  vertical clearance to ventilated soffit located above the ter-

minal within a horizontal distance of 2 feet (60 cm) from the 
edge of the terminal [30 inches (76 cm) minimum]

E=  clearance to unventilated soffit [30 inches (76 cm) minimum]
F=  clearance to outside corner [6 inches (15 cm) minimum]
G=  clearance to inside corner [6 inches (15 cm) minimum]

H=  * not to be installed above a meter/regulator assembly within 

3 feet (90 cm) horizontally from the center-line of the regula-
tor

I=  clearance to service regulator vent outlet [* 6 feet (1.8 m) 

minimum]

J=  clearance to non mechanical air supply inlet to building or 

the combustion air inlet to any other appliance [* 12 inches 
(30 cm) minimum]

K=  clearance to a mechanical air supply inlet [* 6 feet (1.8 m) 

minimum]

L=  ^ clearance above paved side-walk or a paved driveway 

located on public property [* 7 feet (2.1 m) minimum]

M=  clearance under veranda, porch, deck, or balcony [30 inches 

(76 cm) minimum**]

 

^  a vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and 
serves both dwellings*

 

**  only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor*

 

*  as specified in CGA B149 Installation Codes, Note: local Codes or Regulation may require different clearances

 

*  for U.S.A. Installations follow the current National Fuel Gas Code, ANSI Z223.1

AIR SUPPLY INLET

VENT TERMINAL

GAS METER

FIXED

CLOSED

FIXED

CLOSED

OPEN-
ABLE

OPEN-
  ABLE

AREA WHERE TERMINAL 
IS NOT PERMITTED

24

TC30_CE3 250313-44

Vent Terminal Minimum Clearances

     36"

    See Fig. #40b

     48"

 ADJACENT

    24"

 

(91.5 cm)

(61 cm)

(122 cm)

STRUCTURES

OR FENCE

Minimum clearances to the vent terminal must be maintained as shown 
in figure #40 & 41. Measure clearances to the nearest edge of termina-
tion hood.

NOTE:  Vent terminal must not be
recessed 
NOTE:  LOCAL CODES OR REGULATIONS MAY REQUIRE 
 DIFFERENT  CLEARANCES.

 

Roof Pitch Table

   

  (minimum) 

 

                  

 ft 

  m

 Flat to 6/12 

 

1.00 

0.30

 Over 6/12 to 7/12   

1.25 

0.38

 Over 7/12 to 8/12   

1.50 

0.46

 Over 8/12 to 9/12   

2.00 

0.61

 Over 9/12 to 10/12   

2.50 

0.76

 Over 10/12 to 11/12  

3.25 

0.99

 Over 11/12 to 12/12  

4.00 

1.22 

 

VENT TERMINAL MINIMUM CLEARANCES
TO ADJACENT STRUCTURES

Fig. #40

Fig. #40b

Vent Terminal Clearance

Summary of Contents for TC30.CE3

Page 1: ...h other gases unless a certified kit is used This appliance is suitable for installation in a bedroom or bed sitting room FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately c...

Page 2: ...ing Chart 21 Roof Termination Venting 22 Vent Terminal Clearance 24 Vent Terminal Minimum Clearances 24 Vent Pipe Sealant 25 Vent Restrictor Adjustment 26 Firebox Panels Installation 27 Finishing Touch Trim Kit Instructions 28 Lighting Instructions 29 First Fire 29 Maestro Control System 30 Remote Control Initial Setup 30 Maestro Control System Operation 31 Maintenance 34 TC30_C Replacement Parts ...

Page 3: ...be located out of traffic and away from furniture and draperies Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room as the appliance Clothing or other flammable material should not be placed on or near the appli ance Any grill panel or ...

Page 4: ...ly vented gas fuelled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fuelled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and sig...

Page 5: ... 1 Fig 2 Fig 3 MAY USE COMBUSTIBLE FACING MATERIAL IN THIS AREA NON COMBUSTIBLE FINISH MATERIAL SEE FIG 7 NON COMBUSTIBLE ZONE DO NOT INSTALL ANY COMBUSTIBLE MATERIAL ELECTRICAL WIRING OR GAS PLUMBING IN THIS AREA COMBUSTIBLE FRAMING AND FINISH WALL ABOVE STANDOFFS STANDOFFS STEEL FRAMING FIREPLACE FRONT TOP OF LINTEL BAR A B C D E F MANTEL ADJACENT WALL OR MANTEL SUPPORT CEILING UNIT MAY BE RECES...

Page 6: ...eeding Caution The ceramic glass is very fragile and should be handled with care The window frame is held in place by two spring loaded latches that are operated by a one piece latch handle 1 Remove the TC Finishing Touch Trim Kit from the window frame If installed 2 Using a screwdriver or other similar object push against the notch in the top of the latch and grab the bottom of the latch handle a...

Page 7: ...ere gas supply piping may be plumbed Various installations are possible such as into an existing wall a corner a built in wall or a wall projection Fig 7 Due to high temperatures do not locate this fireplace in areas of high traffic or near furniture or draperies The minimum clearances from the fireplace to combustible surfaces must be adhered to and are shown in Fig 2 and Fig 3 Fig 6 TOP STANDOFF...

Page 8: ...ding codes for specific requirements Due to high temperatures non combustible backer board such as cement board or its equivalent must be used to sheet in the front of the fireplace extending 11 1 4 above and 7 to the side of the framing edge bars Fig 9 Standard sheet rock dry wall may be used beyond this If the backer board is not to be finished with other non combustible material such as tiles i...

Page 9: ... MOUNTING AND FINISHING IN STRUCTIONS CLOSELY NON COMBUSTIBLE BOARD NON COMBUSTIBLE BOARD Fig 9 Fig 10 Fig 11 NON COMBUSTIBLE MATERIALS MUST EXTEND 11 1 4 ABOVE AND 7 TO THE SIDES OF THE FRAMING EDGES NON COMBUSTIBLE BOARD MINIMUM COMBUSTIBLE FRAMING DIMENSIONS NOTE FIREPLACE SHOULD BE IN ITS FINAL LOCATION BEFORE FRAMING NON COMBUSTIBLE RECESSED INSTALLATION DETAIL STEEL STUDS NON COMBUSTIBLE MAS...

Page 10: ...ER SIDES 40 1 4 L 2 4 9096 STUD CENTER 12 L 1 5 9295 STUD HEADER 47 5 16 L 1 6 9295 5 STUD PLATE 35 1 16 L 1 7 9294 5 BASE PLATE 7 1 2 L 2 1 Top Frame Assembly Lay out side studs 2 and center stud 4 on a large flat surface Fig 12 Using the screws provided 1 attach the header stud 5 and the plate stud 6 to the center stud 4 TC30 BFRKITB Fig 12 1 2 3 4 5 6 7 10 TC30_CE3 250313 44 TC30 Steel Stud Fra...

Page 11: ...e Assembled Frame to the Unit Align the assembled frame to the unit framing brackets Fig 14 Attach at the fastening points through the access holes in the outer side studs 3 4 Secure to Existing Framing Secure the frame assembly to existing framing through the stud header 5 and the stud plates 7 5 Install non combustible Board Use drywall screws 8 to install the non combustible board Fig 15 Fig 13...

Page 12: ...an 1 will interfere with the window frame Fig 20 12 TC30_CE3 250313 44 Hearth Extension NON COMBUSTIBLE FINISH MATERIAL Fig 20b FRAMING EDGES GLASS FRAME This fireplace may be recessed up to a maximum depth of 6 this recess must be constructed from non combustible material The space between the outside framing edge and the firebox must be completely free of any obstructions or debris and the windo...

Page 13: ...Connect a 110 V AC electrical supply to the outlet installed inside the control box Fig 22 The electrical wires can be accessed from both inside and outside the control box by removing one of the two small access panels fFig 23 The wires from inside the outlet box are connected to the 110 V AC supply Fig 24 5 Connect the gas supply to the valve Fig 22 6 Plug the A C adaptor into the outlet Fig 22 ...

Page 14: ...screwsintheaccess panel and tighten 20 Remove the pressure gauge and the extension test fitting and thread the pressure test port plug into the pressure test port Thread sealant is required on the threads Refer to burner installation manual 21 Turn the fireplace on and verify that the connections are tight Standing Pilot Function Only for use where permitted The control system on this fireplace is...

Page 15: ...disabled and the LED will not flash to indicate low battery The battery backup must be removed when using a power vent The Standing Pilot feature will be de activated feature not available when Power Vent Pre Purge Mode is active Upon receiving any ON command the powerventoutputwillcloseimmediately buttheignitioncyclewillNOTbeginfor10 seconds pre purge This means that themoduleWILLNOTemitasparkand...

Page 16: ... for repair or replacement of the gas valve Check local codes for additional requirements 1 Connect the gas supply to the valve Fig 23 2 Turn on the gas supply and check that all connections are tight and leak free WARNING Use EXTREME CAUTION when using soap and water to do a leak test on the valve fittings There are electronics around and below the valve that can will be damaged if they come in c...

Page 17: ...ined to the boundaries of the chart shown in Fig 35 The horizontal run of vent must have a 1 4 rise for every 1 ft of run towards the termination Before installing venting for this unit the installer should read these instructions to insure that the proper vent configuration has been selected Use only Town and Country Termination kits TCVT WTA Wall Termination Kit TCVT RTA Roof Termination Kit Ven...

Page 18: ... 1 2 opening Properly adjusted the thimble should be flush with the outer wall surface TRIM TO LENGTH Fig 32 Vent System Components Town Country 12 Pipe Length TCVT 811X12 18 Pipe Length TCVT 811X18 24 Pipe Length TCVT 811X24 48 Pipe Length TCVT 811X48 12 Adjustable Pipe Length TCVT 811X12ADJ 45 Elbow TCVT 811XLB45 90 Elbow TCVT 811XLB90 Wall Offset Support TCVT 811XOS Wall Termination Kit TCVT WT...

Page 19: ...sure that both inner and outer pipes are fully engaged and then attach the terminal to the outside wall The vent terminal must not be recessed into the exterior wall or siding 2 Caulk in place to prevent any moisture entering the building NOTE MINIMUM CLEARANCES TO THE VENT TERMINAL MUST BE MAINTAINED see Fig 40 41 Fig 34 HORIZONTAL TERMINAL TCVT 9360 14 1 2 FRAMED OPENING WALL SHIELD THIMBLE TCVT...

Page 20: ...educe horizontal vent run by 2 feet Ensure vent pipe is properly supported All dimensions are approximate Both rise and run may vary with different combinations of pipe 12 Pipe length minimum A Minimum rise B Pipe length C Maximum run D Pipe length Max 52 7 16 1 x 12 34 5 16 1 x 24 64 7 16 1 x 24 46 5 16 1 x 24 1 x12 74 11 16 1 x 24 1 x 12 166 5 16 3 x 48 1 x12 80 11 16 1 x 24 1 x 18 226 5 16 4 x ...

Page 21: ...w or an equal com bination of elbows reduce horizontal vent run by 2 feet Ensure vent pipe is properly supported All dimensions are approximate Both rise and run may vary with different combinations of pipe 12 Pipe length minimum A Minimum rise B Pipe length C Maximum run D Pipe length Maximum 52 7 16 1 x 12 41 1 x 24 64 7 16 1 x 24 51 1 4 1 x 24 1 x 12 74 11 16 1 x 24 1 x 12 167 3 4 3 x 48 1 x 12...

Page 22: ...e Additionally after the vent pipe is in place install a storm collar on top of the shield This will prevent loose insulation from falling into the area between the vent pipe and the shield Vent Pipe 1 Install the first section of vent pipe into the collar on top of the fireplace Secure in place with screws and seal with ap proved HighTemperature self adhesive aluminium tape provided 2 Continueadd...

Page 23: ...collar for a snug fit Apply a thick horizontal ring of mastic around the pipe at top of the storm collar Fig 39 3 Lower the roof vent terminal cap over the vent pipe and secure in place with screws provided Fig 39 Seal screw heads and joint with caulking to prevent any moisture entering the venting system VERTICAL TERMINATION CAP TCVT 9365 FLASHING STORM COLLAR TC42 90665 MASTIC NOTE ADJUSTABLE FO...

Page 24: ...2 1 m minimum M clearance under veranda porch deck or balcony 30 inches 76 cm minimum a vent shall not terminate directly above a side walk or paved driveway which is located between two single family dwellings and serves both dwellings only permitted if veranda porch deck or balcony is fully open on a minimum of 2 sides beneath the floor as specified in CGA B149 Installation Codes Note local Code...

Page 25: ...e sealed with the approved High Temperature self adhesive aluminium tape provided Wrap the tape completely around the joint and press firmly in place Fig 42 APPROVED HIGH TEMP SELF ADHESIVE TAPE VENT PIPE 25 TC30_CE3 250313 Vent Pipe Sealant ...

Page 26: ...configuration of your installation Restrictor positions are based upon lab tests The ideal position may vary slightly with installation Restrictor position is too closed if the flame has the following characteristics Flame is excessively tall and lifting Flame lacks movement Flame soots Restrictor position is too open if the flame has the following characteristics Flame height is low Flame has exc...

Page 27: ...BONE TCPN 30PAC MOUNT VERNON RED HERRINGBONE TCPN 30VRC MANHATTAN BEIGE STACKED BRICK TCPN 30MNC BLACK PORCELAIN TCPN 770 C COFFE BEAN BROWN PORCELAIN TCPN 770CB C See Porcelain panel instruction manual for specific instructions for these panels Before proceeding see burner instructions TC30 PANELS SIDE PANEL RETAINER HEAT SHIELD FIREBOX LIP Fig 44b SCREWS Fig 44c REAR LOWER PANEL ADJUSTABLE V BRA...

Page 28: ...serting the bottom of the panel in first and then angling it up into position It may be necessary to push the firebox shield up to allow panel to move freely into place 4 Install the Rear Upper Panel 5 Install the Left Side Panel by inserting the bottom of the panel in first and then angling it up into position 6 Re install the Side Panel Retainers 7 Install the Left and Right Front Panels HERITAG...

Page 29: ...ot use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance to replace any part of the control system any gas control which has been under water 310106 5051 173 5 TC30 Hot while in operation Do not touch Severe burns may result Keep children clothing furniture gasoline and other liquids having flammable vapours away Keep burner an...

Page 30: ...on again The handset is now synchronized with the fireplace Initial Settings Time and temperature 1 Press and hold the A1 and A2 buttons at the same time until the temperature symbol flashes Fig 48 2 Use the up and down arrows to set pre ferred temperature units F or C 3 PressOKandthe hour valuewillstart to flash 4 Use the up and down arrows to set the hour value 5 Press OK and the minute value wi...

Page 31: ...WN The center button on the remote control can be used to turn the fireplace ON and OFF With the fireplace off press the center button to turn it on The MAN and flame icons will be displayed on the screen A second push will turn it off The MAN and flame icons will disappear from the screen When the fireplace is on the up and down buttons located above and below the center button are used to modula...

Page 32: ...1 weekday ON time Fig 54 2 Use the up and down buttons to change the time to the desired ON time 3 By pressing the OK button the P1 week day OFF time will flash Fig 54 4 Use the up and down buttons to set the desired OFF time 5 Press the OK button and the P2 weekday ON time will flash 6 Repeat the process to set the P2 week day P1 weekend and P2 weekend pro grams 7 When the P2 OFF time is set and ...

Page 33: ...ss and hold the thermostat button on the lower right hand side of the hand held remote for 5 seconds Fig 59 The temperature icon on the display will flash Fig 58 3 While the temperature icon is flashing use the up and down arrows to set the temperature to the desired setting 4 Once the desired setting is reached press the OK button If the OK button is not pressed the icon will continue to flash fo...

Page 34: ...retaining clips Annual Inspection a Remove glass panel and inspect the decorative burner media such as logs pebbles glass etc for soot build up If excessive build up of soot is present have a qualified service person inspect and adjust the unit for proper combustion Clean the decorative media and use a brush or vacuum cleaner to clean the burner paying close attention to the burner ports b Check t...

Page 35: ...0 3 FRAMIMG KIT TC30 FRKIT ITEM DESCRIPTION PART NO 4 PANEL SETS PARK AVE BEIGE HERRINGBONE TCPN 30PAC MT VERNON RED HERRINGBONE TCPN 30VRC MANHATTAN BEIGE STACKED BRICK TCPN 30MNC BLACK PORCELAIN TCPN 770 C C B BROWN PORCELAIN TCPN 770CB C 3 FRAMIMG KIT 3a STEEL STUDS 4 PANEL SETS 4a PANEL LEFT SIDE 4b PANEL UPPER 4c PANEL RIGHT SIDE 4d PANEL LEFT BASE 4e PANEL RIGHT BASE 4f PANEL LOWER BACK KIT ...

Page 36: ...MOUNTING BRACKET 1e IGNITION MODULE 1f WIRING HARNESS 1g MODULE HOLD DOWN BRACKET 1h PRESSURE TEST ASSEMBLY 1i AC ADAPTOR 1j TC36ST PLATE A 1k TC36ST PLATE B 1l WING NUTS 2 1m TC30 MINIMUM RATE SCREW NG 2a INLET PLATE 2b INLET PLATE GASKET 2d 1 2 BULKHEAD FITTING 2e 1 4 BULKHEAD FITTING 2 BULKHEAD ASSEMBLY KIT 2a INLET PLATE 2b INLET PLATE GASKET 2c ELEC BULKHEAD GASKET 2d 1 2 BULKHEAD FITTING 2e ...

Page 37: ...k Black Black Red 120 V olt Hot wire Black 120 V olt Common wire White 1 4 Male Connector 1 4 Male Connector 1 4 Male Connector 1 4 Male Connector 1 4 Female Connector 1 4 Female Connector 1 4 Female Connector 1 4 Female Connector Wiring the Power V ent Kit provided by T own Country Communication wires Main Pilot Low pressure side egnarO egnarO Pressure switch wire Supplied Power V ent switch wire...

Page 38: ...KET TCVT 93915 STORM COLLAR TC42 90665 WALL SHIELD CEILING FIRESTOP TCVT THIMA Fig 63 WALL TERMINAL TCVT 9360 WALLSHIELD CEILING FIRESTOP THIMBLE TCVT THIMA Fig 61 Fig 62 38 TC30_CE3 250313 44 Wall Termination Kit TCVT THIMA Wall Shield Ceiling Firestop Thimble TCVT RTA Roof Termination Kit ...

Page 39: ... 5 16 15 7 8 7 16 1 5 16 8 5 16 13 13 16 12 9 16 13 1 8 11 1 8 TCVT 811X12ADJ TCVT 811XLB45 TCVT 811XLB90 TCVT 811X _ _ 12 PIPE 10 1 4 18 PIPE 16 1 4 24 PIPE 22 1 4 48 PIPE 46 1 4 Fig 64 39 TC30_CE3 250313 Vent Pipe Dimensions ...

Page 40: ...22 3 8 24 PIPE 27 1 8 26 1 2 48 PIPE 44 1 16 43 1 2 Fig 65 ADDING AN ADJUSTABLE SECTION TO PIPE WILL INCREASE OFFSET BY 2 1 8 TO 6 3 4 A B C 12 PIPE 13 7 16 23 1 4 18 PIPE 17 9 16 27 5 8 24 PIPE 21 7 8 31 3 4 48 PIPE 38 3 4 44 7 8 A B 12 PIPE 29 18 PIPE 35 24 PIPE 41 48 PIPE 65 ADDING AN ADJUSTABLE SECTION TO PIPE WILL INCREASE OFFSET BY 3 TO 9 1 2 40 TC30_CE3 250313 44 Vent Offset Chart ...

Page 41: ...TS TERMINAL BLOCK B FLOOR LIGHTS White White Black Black Fig 66 Light Bulb Replacement 1 Replacement bulbs should only be G6 35 T4 75Watt 2 Remove the screw holding the glass cover in place 3 Use a flat blade screw driver to pull down the end of the cover and remove Fig 67 4 DO NOT TOUCH THE BULB DIRECTLY Use latex gloves or paper towel to remove bulb and replace 5 Replace cover and secure with sc...

Page 42: ...42 TC30_CE3 250313 44 Notes ...

Page 43: ...E3 250313 NOTE The Safety Label is located on a plate found in a slot between the left hand side lintel and the left hand side window frame This plate is attached to the lintel with a cable Safety Label Location ...

Page 44: ...Printed in Canada Technical support 1 250 748 1184 Web site www townandcountryfireplaces net 2975 Allenby Rd Duncan BC V9L 6V8 ...

Reviews: