- 27 -
Important
•
After giving the impulse to automatically program the end positions, no other impulse must be given. Also the
safety devices mustn´t be triggered. This would lead to an interruption of the programming process.
•
Therefore, the mechanical stops must be set so that the existing contact strips cannot be triggered.
G
safety edge LL1
(terminals
Z2
(left): 50/52 and Jumper
JF = set
)
Safety edges
not active:
8,2kΩ
safety edge 1, left leaf
should not be evaluated.
opening active:
8,2kΩ
safety edge 1, left leaf
should be evaluated
at opening.
closing active:
8,2kΩ
safety edge 1, left leaf
should be evaluated
at closing.
opening / closing:
8,2kΩ
safety edge 1, left leaf
should be evaluated
at opening and closing.
G
safety edge LL2
(terminals
Z2
(left): 50/53 and Jumper
JF = set
)
Safety edges
not active:
8,2kΩ
safety edge 2, left leaf
should not be evaluated.
opening active:
8,2kΩ
safety edge 2, left leaf
should be evaluated
at opening.
closing active:
8,2kΩ
safety edge 2, left leaf
should be evaluated
at closing.
opening / closing:
8,2kΩ
safety edge 2, left leaf
should be evaluated
at opening and closing.
G
safety edge RL1
(terminals
Z2
(right): 50/52 and Jumper
JF = not set
)
Safety edges
not active:
8,2kΩ
safety edge 1, right leaf
should not be evaluated.
opening active:
8,2kΩ
safety edge 1, right leaf
should be evaluated
at opening.
closing active:
8,2kΩ
safety edge 1, right leaf
should be evaluated
at closing.
opening / closing:
8,2kΩ
safety edge 1, right leaf
should be evaluated
at opening and closing.
G
safety edge RL2
(terminals
Z2
(right): 50/53 and Jumper
JF = not set
)
Safety edges
not active:
8,2kΩ
safety edge 2, right leaf
should not be evaluated.
opening active:
8,2kΩ
safety edge 2, right leaf
should be evaluated
at opening.
closing active:
8,2kΩ
safety edge 2, right leaf
should be evaluated
at closing.
opening / closing:
8,2kΩ
safety edge 2, right leaf
should be evaluated
at opening and closing.
status: not triggered
status: triggered
status: contact strip not connected
or defect
status: contact strip deactivated in menu
$
o
$
x
$
$
-
e.g.
$$$$$$$$$$$$$$$$
$$$$$$$$$$$$$$$$
LL1 LL2 RL1 RL2
SE-status display
Safety edges
Status dsplay of safety sensing edges
LL1
left leaf (1)
RL1
right leaf (1)
LL2
left leaf (2)
RL2
right leaf (2)