6.29 Control panel parameters
6.29.1 Prohibiting the change of parameter settings
:
Prohibition of parameter setting
■
Setting method
:
Allowed
・・・・・・
No parameters are write-protected. (Default setting)
:
Prohibited
・・・・
All parameters except for
are write-protected.
[
Parameter setting
]
Title
Function
Adjustment range
Default setting
Prohibition of parameter setting
:
Allowed
:
Prohibited
■
Canceling method
only is designed so that its setting can be changed anytime even when it is set at
.
■
To prohibit all operation, including key operation, use the parameter
(Panel operation
prohibition).
6.29.2 Changing the units of display
:
Current / voltage display mode
■
Example of setting
When the VFP7-2185P (rated current: 73A) is operated under the rated 100% load :
1) Display in [%]
2) Display in [A] or [V]
Title
Function
Adjustment range
Default setting
Current / voltage display
mode
: [%]
: [A] or [V]
・
Function
This parameter is used to change the units of display of current and voltage.
Display in % <=> Display in A (ampere) or V (volt)
Output current
: 73.0A
Input voltage
: 200V
DC voltage
: 100%
Output current
: 100%
※
With
, you can convert the units pertaining to the following parameters:
・
Display in [A]: Current monitor
Motor overload protection level #1,#2,#3,#4
,
,
,
DC injection braking current
Stall prevention level
・
Display in [V]: Voltage monitor
V/f 5-point setting
,
,
,
,
(
Note
)
Base frequency voltage is always displayed in voltage unit.
・
Function
This parameter is used to make a setting to prohibit or allow the change of parameter settings.