[11] Jumper frequency
Vector control
Title
Communi
cation No
Function
Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
Torque
control
Position
control
V/f
Constant
Reference
section
0270
Jump frequency #1
0.0
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
6.10
0271
Jump frequency band #1
0.0
〜
30.0 [Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
6.10
0272
Jump frequency #2
0.0
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
6.10
0273
Jump frequency band #2
0.0
〜
30.0 [Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
6.10
0274
Jump frequency #3
0.0
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
6.10
0275
Jump frequency band #3
0.0
〜
30.0 [Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
6.10
0276
Object of jump frequency process 0: Process amount, 1: Output frequency
−
0
Enabled
●
/
●
−
−
●
6.10
[12] Preset speed operation frequency (8- to 15-stage speed)
Vector control
Title
Communi
cation No
Function
Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
Torque
control
Position
control
V/f
Constant
Reference
section
0287
Preset-speed #8
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
5.14
0288
Preset-speed #9
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
5.14
0289
Preset-speed #10
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
5.14
0290
Preset-speed #11
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
5.14
0291
Preset-speed #12
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
5.14
0292
Preset-speed #13
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
5.14
0293
Preset-speed #14
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
5.14
0294
Preset-speed #15
〜
[Hz]
0.01/0.01
0.0
Enabled
●
/
●
−
−
●
5.14
[13] PWM carrier frequency
Vector control
Title
Communi
cation No
Function
Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
Torque
control
Position
control
V/f
Constant
Reference
section
0300
PWM carrier frequency
0.5
〜
15.0(8.0, 5.0) [kHz] (*1)
0.1/0.001 See J-28 Disabled
●
/
●
●
/
●
−
/
●
●
6.12
(*1)Upper limits differ by applicable motor capacity. For details, refer to 6.12.
Carrier frequency is automatically limited to less than 10kHz when operation frequency is more than 130Hz.
[14] Tripless intensification setup (1/2)
Vector control
Title
Communi
cation No
Function
Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
Torque
control
Position
control
V/f
Constant
Reference
section
0301
Auto-restart
0: Disabled, 1: Enabled(at power failure),
2: Enabled(at ST ON/OFF), 3: Enabled(1+2)
−
0
Enabled
●
/
●
●
/
●
−
/
●
●
6.13.1
0302
Regenerative power ride-through
control / Deceleration stop
0: OFF, 1: ON, 2:ON(Deceleration stop)
−
0
Enabled
●
/
●
−
/
−
−
/
−
●
6.13.2
0303
Retry selection
0: Disabled, 1 to 10 times
−
0
Enabled
●
/
●
●
/
●
−
/
●
●
6.13.3
0304
Dynamic braking mode selection 0: Disabled, 1: Enabled/overload detection enabled
−
See J-28 Enabled
●
/
●
●
/
●
−
/
●
●
6.13.4
0305
Over-voltage stall protection
0: Enabled, 1: Disabled,
2: Enabled (Forced quick deceleration)
−
0
Enabled
●
/
●
●
/
●
−
/
●
●
6.13.5
0306
Base frequency voltage #1
(output voltage adjustment)
0.0
〜
600.0 [V]
0.1/0.1
See J-28 Enabled
●
/
●
●
/
●
−
/
●
●
6.13.6
Sensorless vector/vector with sensor (
●
valid,
−
:invalid)