![Toshiba TOSVERT VF-P7 Instruction Manual Download Page 171](http://html.mh-extra.com/html/toshiba/tosvert-vf-p7/tosvert-vf-p7_instruction-manual_424933171.webp)
G-4
■
Table of contact input terminal function settings
Parameter setting
Parameter setting
Positive
logic
Negative
logic
Function
Positive
logic
Negative
logic
Function
0
1
No assignment function
70
71
Reservation area(*3)
2
3
F: Forward operation command
72
73
Reservation area(*3)
4
5
R: Reverse operation command
74
75
Reservation area(*3)
6
7
ST: Standby (Inverse)
76
77
Reservation area(*3)
8
9
RES: Reset
78
79
Reservation area(*3)
10
11
S1: Preset-speed #1
80
81
Reservation area(*3)
12
13
S2: Preset-speed #2
82
83
Reservation area(*3)
14
15
S3: Preset-speed #3
84
85
Reservation area(*3)
16
17
S4: Preset-speed #4
86
87
Binary data write
18
19
Jog run
88
89
Up/down frequency (up) (*1)
20
21
Emergency stop
90
91
Up/down frequency (down) (*1)
22
23
DC injection breaking
92
93
Up/down frequency (clear)
24
25
Acceleration/deceleration
switching #1(*2)
94
95
PUSH-type run command
26
27
Acceleration/deceleration
switching #2(*2)
96
97
PUSH-type stop command
28
29
V/f switching #1(*2)
98
99
Forward/reverse selection
30
31
V/f switching #2(*2)
100
101
Run/stop command
32
33
Torque limit switching #1(*2)
102
103
Commercial power/INV switching
34
35
Torque limit switching #2(*2)
104
105
Frequency reference priority
switching
36
37
PID control OFF selection
106
107
VI/II terminal priority
38
39
Pattern group #1
108
109
Command terminal board priority
40
41
Pattern group #2
110
111
Parameter editing enabling
42
43
Pattern group #3
112
113
Control switching (torque,
position)
44
45
Pattern group #4
114
115
Deviation counter clear
46
47
Pattern run continuation signal
116
117
Position control forward limit LS
48
49
Pattern run trigger signal
118
119
Position control reverse limit LS
50
51
Forced Jog forward operation
120
121
Light load high-speed operation
enabling
52
53
Forced Jog reverse operation
122
123
Reservation area(*3)
54
55
Reservation area(*3)
124
125
Preliminary excitation
56
57
Reservation area(*3)
126
127
System consistent sequence
(BC: Braking command)
58
59
Reservation area(*3)
128
129
System-supporting sequence
(B: Brake release)
60
61
Reservation area(*3)
130
131
System-supporting sequence
(BA: Brake answer)
62
63
Reservation area(*3)
132
133
System-supporting sequence
(BT: Brake test)
64
65
Reservation area(*3)
134
135
Reservation area(*3)
66
67
Reservation area(*3)
68
69
Reservation area(*3)
(*1): Valid when
(Speed setting mode selection) is set at
(Up-down frequency).
The frequency setting range is between 0.0 to
(Upper limit frequency).
In this case, acceleration time is
(Acceleration time #2), and deceleration time is
(Deceleration time #2).
(*2): To switch acceleration/deceleration pattern, V/f pattern, torque limit #1
〜
#4, give the
following signals to switching functions. (in case of positive logic)
switching #1
switching #2
Acc/dec, V/f, torque limit #1
OFF
OFF
Acc/dec, V/f, torque limit #2
ON
OFF
Acc/dec, V/f, torque limit #3
OFF
ON
Acc/dec, V/f, torque limit #4
ON
ON
(*3): Reservation area. Do not set at these functions.
■
Sink logic/source logic
Switching between sink logic and source logic (input/output terminal logic) is possible.
For details, refer to the section 2.3.2.