E-7
[Set value]
: VI/II input
Speed commands are entered by means of external signals (terminal VI: 0 to 10 Vdc
or terminal II: 4 to 20 mAdc).
: RR input
Speeds commands are entered by means of external signals (terminal RR: 0 to 10Vdc).
: RX input
Speed commands are entered by means of external signals (terminal RX: 0 to
+/-10 Vdc (+/-5 Vdc).
: RX2 control
Speed commands are entered by means of external signals (terminal RX2 (optional):
0 to +/-10 Vdc (+/-5 Vdc)).
: Operating panel input enabled
Frequencies are set by pressing the key on the control panel or an
extended control panel (optional).
: Binary/BCD input
Speed commands are entered from 12/16-bit binary input(optional) or a BCD (optional).
: Communication common serial option
Speed commands are entered from an RS232C device (optional) or terminal board-
equipped RS485 device (optional).
→
Communication number: FA01
: Communication RS485
Speed commands are entered from the RS485 communication device fitted as standard.
→
Communication number: FA00
: Communication add-on module option
Speed commands are entered from the network communication device
TOSLINE-F10M or S20 (optional).
: Up-down frequency
Speed commands are entered by means of up-down frequency signals from the
terminal board (refer to 7.2).
: Pulse input
Speed commands are entered by means of pulses (optional).
☆
The following communication devices are optionally available.
・
RS232C (Type: RS2001Z)
・
RS485 (Type: RS4001Z. Up to 64 units can be connected.)
・
TOSLINE-F10M/TOSLINE-S20
・
Device Net (On the drawing board)
・
Profi Bus (On the drawing board)
☆
The functions assigned to the following control terminals (contact input: Refer to 7.2.)
are always activated regardless of the settings of the control device selection
parameter
and the speed command selection parameter
.
・
Reset terminal (assigned to RES by default, enabled only when the invertor trips)
・
Standby terminal (assigned to ST by default)
・
Emergency stop terminal
☆
Be sure to put the inverter out of operation before changing the control device selection
parameter
or the speed command selection parameter
, though no change
can be made to them if the inverter is in operation.
■
Preset speed operation
: Set this parameter at
(terminal board).
: Any setting is valid.
▲
▼