G-9
7. 2. 3 Setup of input/output terminal operation time
■
Setup of response time
Title
Function
Adjustment range
Default value
Input terminal #1 response time (F)
〜
[ms]
Input terminal #2 response time (R)
〜
[ms]
Input terminal #3 response time (ST)
〜
[ms]
Input terminal #4 response time (RES)
〜
[ms]
Input terminal #5
〜
8 response time
〜
[ms]
Input terminal #9
〜
16 response time
〜
[ms]
Output terminal #1 delay time (OUT1)
〜
[ms]
Output terminal #2 delay time (OUT2)
〜
[ms]
Output terminal #3 delay time (FL)
〜
[ms]
Output terminal #4 delay time
〜
[ms]
Output terminal #5 delay time
〜
[ms]
Output terminal #6 delay time
〜
[ms]
Output terminal #7 delay time
〜
[ms]
Output terminal #1 holding time (OUT1)
〜
[ms]
Output terminal #2 holding time (OUT2)
〜
[ms]
Output terminal #3 holding time (FL)
〜
[ms]
Output terminal #4 holding time
〜
[ms]
Output terminal #5 holding time
〜
[ms]
Output terminal #6 holding time
〜
[ms]
Output terminal #7 holding time
〜
[ms]
:
Setting when vector option unit or expansion TB option unit is used.
Note): The minimum setting unit is 2.5 ms. Please input the value which omitted below the decimal point of
a multiple of 2.5.
7. 2. 4 Analog input filter
■
Response time setting
Title
Function
Adjustment range
Default value
Analog input filter
(Disabled) to
(maximum filter capacity)
・
Function
The input/output terminal operation time setup function is used to extend response time if
there is something malfunctioning because of noise or chattering of input relay.
For each output terminal, delay time at turning on or off can be set individually.
・
Function
This function is effective to remove noise from the frequency setting circuit. If operation is unstable
because of noise, increase the time constant of the analog input filter.