Basic Installation and Operation Guide
TE Series Digital Solid State Soft Starters 18 – 1250A
31 |
P a g e
5.5.3
Jog Mode Functions
5.5.4
Kick Start Mode Functions
5.5.5 Decel Mode Functions
5.5.6 Restart Function
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F019
Jog M
odes
Voltage Jog
5 – 100% Line Voltage
1%
50%
5.6.3
and
4.2.5.b
F020
Time of Voltage Jog
1 – 20 Seconds
1 second
10
seconds
F021
Current Jog
100 – 500% Motor Current
1%
150%
Table 5.5.3: Jog Mode Function Group
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F022
Kick Mo
de
Kick Start Voltage
0 = Disabled, or
10 - 100% Line Voltage
1%
0
Disabled
5.6.4
F023
Kick Start Time
0.1 - 2 Seconds
0.1second
0.8
seconds
Table 5.5.4: Kick Start Mode Function Group
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F024
Pump Flex Dec
e
l
Mode
Pump Flex Control /
Deceleration Ramp
0 = Disabled (coast to stop)
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even
if there is an OL trip
1
0
Disabled
5.6.5
and
Append.
2
F025
Begin Decel Level (BDL),
Immediate Drop Down Torque
0 - 100 % of Output Voltage
1%
60%
F026
Decel Shut Off Voltage
0 to (BDL minus 1)% Voltage
1%
30%
F027
Decel Ramp Time
1 – 60 Seconds
1 second
10
seconds
Table 5.5.5: Pump Flex Decel Mode Function Group
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F028
Restart
Restart Delay Time
(Sequential Start Delay)
0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)
1 second
0
Disabled
5.6.6
F029
Reserved for Factory Use
Table 5.5.6: Restart Function Group
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]