Basic Installation and Operation Guide
TE Series Digital Solid State Soft Starters 18 – 1250A
1 |
P a g e
Chapter 1 - Introduction
1.1 General Description
The
TE Series
is a digitally programmable solid-state reduced voltage
soft starter. Its six SCR design features a voltage/current ramp with an
anti-oscillation circuit for smooth load acceleration. The SCRs are sized
to withstand starting currents of 500% for 60 seconds. The
TE Series
features smooth, step-less ramp control, which reduces motor inrush
current and excessive wear on the mechanical drive train components.
The
TE Series
includes a programmable keypad for setting operating
parameters for the ideal starting cycle and protection features, plus easy
to understand diagnostic LEDs. Starting torque, ramp time, current limit,
dual ramp, and Decel control are standard features on the
TE Series
. By
simply adjusting the unit’s starting torque, ramp time and current limit
functions, the starting electrical characteristics of the motor can be
matched to the mechanical characteristics of the drive train for controlled
acceleration of the load. The
TE Series
includes solid-state electronic
overload protection in addition to numerous other protective features. It
requires 120VAC (220VAC optional) control power and uses dry contact
inputs for Start / Stop control. Programmable auxiliary contacts and
provisions for interlocking are also included.
1.1.1 Control Features
Acceleration Adjustments
Programmable Ramp Types:
Voltage Ramp (VR) or closed loop Current Ramp (CR)
Starting Torque: 0 - 100% of line voltage (VR)
or 0 - 600% of motor FLA (CR)
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 600% (VR or CR)
Dual Ramp Settings
4 Options:
Ramps 1 & 2 = VR,
Ramp 1 = VR, Ramp 2 = CR,
Ramps 1 & 2 = CR;
Ramp 1 = CR, Ramp 2 = VR
Dual Ramp Control:
Ramp #1 = Default,
Ramp #2 = Selectable via dry contact input
Deceleration Adjustments
Begin Decel Level: 0 - 100% of line voltage
Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds
Programmable to Decel or coast to stop upon overload trip
Jog Settings
Jog function selected via dry contact closure input.
Jog Voltage: 5 - 100%
Time of Jog Voltage: 1 - 20 seconds
Jog Current: 100 - 500%
Kick Start Settings
Kick Voltage: 10 - 100%
Kick Time: 0.1 - 2 seconds
Real Time Clock (RTC)
Controller
24/7 Time Clock Controller
Range: 1-24 hours, and 1- 7 days per week,
1 - 7 start events per day, works with Process Timer for run time