Basic Installation and Operation Guide
TE Series Digital Solid State Soft Starters 18 – 1250A
35 |
P a g e
5.5.12 Fault History and Run Time
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F085
Fault
Hist
ory a
n
d Ru
n Da
ta
Fault History #1, Latest Fault
0 = No fault history, or
Fault # 1 - 27: see Fault code list
1 0
5.6.12
F086
Time Stamp, Fault #1
Based on F078-80
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
00.01 00.00
F087
Date Stamp, Fault #1
Based on F076-77
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
00.01 01.01
F088
Fault History #2, Previous
Fault
0 = No fault history, or
Fault # 1 - 27: see Fault code list
1 0
F089
Time Stamp, Fault #2
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
00.01 00.00
F090
Date Stamp, Fault #2
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
00.01 01.01
F091
Fault History #3, Oldest Fault
0 = No fault history, or
Fault # 1 - 27: see Fault code list
1 0
F092
Time Stamp, Fault #3
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
00.01 00.00
F093
Date Stamp, Fault #3
01.01 – 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
00.01 01.01
F094
Run Time, Hours
000.0 – 999.9 hours
0.1 hours
0
5.6.12.
a
F095
Run Time,
1000 Hour Overflow
0000 – 9999 thousand hours
1 k-hour
0
F096
Run Cycle Counter
0000 – 9999 times
1 times
0
F097
Run Cycle Counter
10K overflow
0000 – 9999 10 thousand times
10k times
0
Table 5.5.12: Fault History and Run Data Group