38
RemotEye® ESS Instruction Manual
– 201791-002
Name
RN
Type
Units*
Bit 15 Bit 14 Bit 13 Bit 12
Bit 11 Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Right string charge
current
40036
Real
Time
x0.01 Amps
Right string current value in the charge direction is indicated by 0.01A/LSB (655.35A to 0A)
Right string
discharge current
40037
Real
Time
x0.01 Amps
Right string current value in the discharge direction is indicated by 0.01A/LSB (655.35A to 0A)
Left string min. cell
temp. / module No.
40038
Real
Time
Temperature
Unit
Left string min. temp. value / of all cells indicated by 1°C/LSB.
Usage range -40°C to 125°C
Module No. containing the minimum cell temperature value in Left string. Usage range: module No. 1
to 28.
Left string max. cell
temp. / module No.
40039
Real
Time
Temperature
Unit
Left string max. temp. value / of all cells indicated by 1°C/LSB.
Usage range -40°C to 125°C
Module No. containing the maximum cell voltage value in Left string. Usage range: module No. 1 to
28.
Right string min. cell
temp. / module No.
40040
Real
Time
Temperature
Unit
Right string min. temp. value / of all cells indicated by 1°C/LSB.
Usage range -40°C to 125°C
Module No. containing the minimum cell temperature value in Right string. Usage range: module No.
1 to 28.
Right string max.
cell temp. / module
No.
40041
Real
Time
Temperature
Unit
Right string max. temp. value / of all cells indicated by 1°C/LSB.
Usage range -40°C to 125°C
Module No. containing the maximum cell voltage value in Right string. Usage range: module No. 1 to
28.
Left & Right string
average cell temp.
40042
Real
Time
Temperature
Unit
Left string average temp. value of all cells indicated by 1°C/LSB.
Usage range -40°C to 125°C
Right string average temp. value of all cells in indicated by 1°C/LSB. Usage range -40°C to 125°C
Left string min. cell
voltage
40043
Real
Time
x0.001 Volts
Left string min. voltage value of all cells indicated by 1mV/LSB
Left string max. cell
voltage
40044
Real
Time
x0.001 Volts
Left string max. voltage value of all cells indicated by 1mV/LSB
Left string min./max.
cell voltage module
No.
40045
Real
Time
x1
Module No. containing the minimum cell voltage value in Left string.
Usage range: module No. 1 to 28.
Module No. containing the maximum cell voltage value in Left string.
Usage range: module No. 1 to 28.
Right string min. cell
voltage
40046
Real
Time
x0.001 Volts
Right string min. voltage value of all cells indicated by 1mV/LSB
Right string max.
cell voltage
40047
Real
Time
x0.001 Volts
Right string max. voltage value of all cells indicated by 1mV/LSB
Right string
min./max. cell
voltage module No.
40048
Real
Time
x1
Module No. containing the minimum cell voltage value in Right
string.
Usage range: module No. 1 to 28.
Module No. containing the maximum cell voltage value in Right string.
Usage range: module No. 1 to 28.
Left String Battery
Actual Charge
40049
Real
Time
x0.001 mAh
Left String Battery Actual Charge
Left String Battery
Actual Capacity
40050
Real
Time
x0.001 mAh
Left String Battery Actual Capacity
Right String Battery
Actual Charge
40051
Real
Time
x0.001 mAh
Right String Battery Actual Charge
Right String Battery
Actual Capacity
40052
Real
Time
x0.001 mAh
Right String Battery Actual Capacity
Left String SOC(%)/
Avg Cell Temp
40053
Real
Time
x1 % /
Temperature
Unit
Left String SOC(%)
Avg Cell Temp
Right String SOC(%)/
Avg Cell Temp
40054
Real
Time
x1 % /
Temperature
Unit
Right String SOC(%)
Avg Cell Temp
Left String (BMU1) Cell Level View Registers
Module 1
Cell Voltage Cell 1/2
40086
Real
Time
x0.001 Volts
Module 1
Cell Voltage Cell 1
Summary of Contents for RemotEye ESS
Page 2: ......
Page 16: ...10 RemotEye ESS Instruction Manual 201791 002 ...
Page 35: ...RemotEye ESS Instruction Manual 201791 002 29 ...
Page 82: ...76 RemotEye ESS Instruction Manual 201791 002 ...
Page 83: ...RemotEye ESS Instruction Manual 201791 002 77 This Page Left Intentionally Blank ...
Page 84: ......
Page 85: ......