87
NMS (Manager) Settings
There are two areas of consideration when coordinating an NMS with a RemotEye II.
First, the Manager software on the NMS must be prepared to handle the RemotEye II
Management Information Base (MIB), and second, the Manager must be configured
to receive any traps the RemotEye II sends.
Importing the MIB File
The MIB file, Toshiba.mib, is contained on the included CD-ROM. This file
describes the information that is attainable from a Toshiba UPS.
The Toshiba MIB file must be manually entered (imported or compiled) into the
Manger database. For instruction on incorporating private MIB files into the
Manager, consult the Manager software documentation.
Prior to importing the Toshiba MIB file, the MIB file RFC1213.MIB (not provided)
must also be imported. This file outlines the SNMP MIB-II standard used by
RemotEye II.
MIB Import Example
This example shows how to incorporate the Toshiba MIB into the Manager
application HP OpenView Workgroup Node Manager. The software runs on the
Windows platform.
Launch HP OpenView Workgroup Node Manager.
From the Control pull down menu, click SNMP Manager
→
Manage Database
→
Select
→
(map to the MIB file, Toshiba.mib, on the included CDROM)
→
click
ADD.
Click Close to close the SNMP Manager Database.
Specifying Trap Receivers
To send traps to an NMS, the NMS must be designated as a trap receiver of the
RemotEye II. See Trap Receiver Table section on page 40 for instruction on defining
a trap receiver.